2013-11-22 18:16:03 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- PROVIDE REVISED GEOTECHNICAL REPORT THAT REFLECTS |
| THE ACTUAL PROPOSED 2 STORY CONCRETE BLOCK RESIDENCE |
| AND THE INGROUND POOL IN CLOSE PROXIMITY TO THE |
| BUILDING AS SHOWN ON THE SURVEY. SEE PROPOSED PLANS FOR |
| THE ACTUAL SQUARE FOOTAGE OF THE HOUSE AND ALL COLUMNS |
| SHOWN. SEC. R401.4 OF 2010 FBC-RESIDENTIAL AND SEC. |
| 107.2.1.3 CITY AMENDMENTS TO FBC. |
| |
| 2- SPECIFY ON PLANS CARBON MONOXIDE ALARMS. SEC. R315 |
| OF 2010 FBC-RESIDENTIAL. |
| |
| 3- SPECIFY THE ATTIC ATTIC LIVE LOAD AS REQUIRED BY |
| TABLE R301.5 AND FOOTNOTES "B" AND "G". |
| |
| 4- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR CONSTRUCTION OF SECOND FLOOR WALL ABOVE GARAGE |
| AREA. SPECIFY ALL WALL FRAMING FRAMING MEMBERS, ALL |
| BEAMS AND COLUMNS SUPPORTING THE BEAMS AND CONNECTORS. |
| SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| |
| 5- SPECIFY FIRE RATING SPECIFICATIONS FOR GARAGE DOOR |
| #5 AS REQUIRED BY SEC. R302.5.1 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 6- PROVIDE COMPLETE STRUCTURAL BUCK DETAILS AND |
| SPECIFICATIONS FOR GARAGE DOORS, ALL EXTERIOR SWING |
| DOORS AND WINDOWS. SEC. R612.10.2 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 7- PROVIDE FRAMING DETAILS AND SPECIFICATIONS FOR ALL |
| ARCHED OPENINGS SHOWN ON PLANS. SEC. R301.1 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| INTERIOR BEARING WALL FOOTING. SEC. R301.1 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 9- SPECIFY STAIR FIREBLOCKING. SEC. R302.11 |
| 2010-FBC-RESIDENTIAL. |
| |
| 10- COMPLETE DETAIL/SPECS FOR INTERIOR COLUMN BY |
| STAIRWAY. SPECIFY SIZE AND ALL CONNECTORS. SEC. R301.1 |
| OF 2010 FBC-RESIDENTIAL. |
| |
| 11- PROVIDE COMPLETE ENGINEERING CALCULATIONS FOR REAR |
| PORCH COLUMNS FOOTING SIZE AS SHOWN ON PLANS. SEC. |
| R301.1 OF 2010 FBC-RESIDENTIAL. |
| |
| 12- PROVIDE COMPLETE SECOND FLOOR FRAMING PLAN. SPECIFY |
| ALL BEAMS, HEADERS, LINTELS, ALL PORCH BEAMS AND END |
| CONNECTORS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| |
| 13- A) PROVIDE COMPLETE ROOF FRAMING PLAN SHOWING ALL |
| BEAMS, LINTELS, HEADERS, ETC. INCLUDING THE ROUND ROOF |
| ABOVE BEDROOM #3. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| |
| B) PROVIDE COMPLETE WOOD FRAMING DETAILS AND FASTENING |
| SPECIFICATIONS FOR THE CONSTRUCTION OF KNEE WALL ABOVE |
| BEDROOM #3. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| |
| 14- SHEET S-1: |
| A) SPECIFY VAPOR BARRIER. SEC. R405.2.2 OF 2010 |
| FBC-RESIDENTIAL. |
| B) FOOTING SHOWN ON FOUNDATION PLAN DOESN'T MATCH |
| FOOTING SHOWN ON TYPICAL 2 STORY WALL SECTION. IS IT |
| MONOLITHIC FOOTING OR STEMWALL?. SEC. 107.2.1 CITY |
| AMENDMENTS TO FBC. |
| C) SPECIFY CONNECTORS FOR ALL TRUSS GIRDERS SHOWN ON |
| FRAMING PLANS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| D) PROVIDE COMPLETE DETAIL/SPECS FOR SOFFIT DETAIL. |
| WHERE IS THE METHAL LATH ATTACHED TO. SEC. R703.1.3 OF |
| 2010 FBC-RESIDENTIAL. |
| E) SPECIFY WALL INSULATION (CONCRETE BLOCK AND FRAMED |
| WALLS), INSULATION ABOVE GARAGE. COORDINATE WITH THE |
| ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| CONSERVATION. |
| F) SPECIFY FIREBLOCKING. ON SECOND FLOOR AND ON WALLS. |
| SEC. R302.11 OF 2010 FBC-RESIDENTIAL. |
| G) FLORIDA PRODUCT APPROVAL NUMBER FOR SIMPSON CAP AND |
| BASE CONNECTORS SHOWN ON SECTION 1/S-1 IS NO CURRENT. |
| PROVIDE CURRENT 2010 CODE VERSION. DCA RULE 9N-3. |
| H) PORCH FOOTING SIZE SHOWN ON FOUNDATION PLAN DOESN'T |
| MATCH SECTION 1/S-1. SEC. 107.2.1 CITY AMENDMENTS TO |
| FBC. |
| |
| 15-FLOOD ZONE A5. |
| A) SPECIFY FINISH FLOOR ELEVATION AT GARAGE AND FIRST |
| FLOOR. |
| B) ELEVATION CERTIFICATES REQUIRED DURING CONSTRUCTION |
| AND FINAL. |
| |
| 16- DRAINAGE PLAN ON SHEET A-6 SHOWS 4" DECK DRAIN ON |
| BACK PART OF BUILDING BY THE NEW POOL AREA. DRAWINGS ON |
| SHEET S-2 SHOWS SLOPE TOWARDS THE POOL. COORDINATE AS |
| REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| |
| 17- SHEET S-2: PROVIDE ENGINEERING CALCULATIONS FOR |
| RETAINING WALLS FOR POOL AND 2 STORY BUILDING. SEC. |
| R301.1 OF 2010 FBC-RESIDENTIAL AND SEC. 107.2.1.3 CITY |
| AMENDMENTS TO FBC. |
| |
| 18- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) ARCHED ENTRY WOOD DOOR AS SHOWN ON PLANS. |
| |
| B) ROOF TILE ADHESIVE. NOA 10-1112.05 SUBMITTED WAS |
| SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. |
| |
| C) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL |
| COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR. |
| |
| 19- PERSON RESPONSIBLE FOR THE DESIGN TO APPROVE IN |
| WRITING ALL PRODUCT APPROVALS AS REQUIRED BY SEC. |
| 107.3.4.1 OF CITY AMENDMENTS. |
| |
| 20- ENERGY CALCULATIONS: |
| A) REVISE THE DOORS INFORMATION ON PAGE 3 OF 6 TO MATCH |
| PLANS AND PRODUCT APPROVALS SUBMITTED. SEE NUMBER, TYPE |
| AND SIZE OF WINDOWS SHOWN ON PLANS. FOR EXAMPLE THE |
| ENTRY DOOR IS THE ONLY WOOD DOOR AND IS ONLY ONE. SEC. |
| 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| B) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF ENERGY |
| CALCULATIONS FORM. SEC. 103.2.3.2 OF 2010 FBC-ENERGY |
| CONSERVATION. |
| |
| 21- REVISE ATTIC ACCESS DETAIL ON SHEET A-3: NEED 22" |
| MIN. OPENING. SEE SEC. R807.1 OF 2010 FBC-RESIDENTIAL. |
| |
| 22- SHEET A-5: |
| A) REVISE PLYWOOD SHEATHING NAILING SCHEDULE FOR ROOF. |
| ROOF NAILING ZONES ARE INCORRECT. SEE FIGURE R301.2.(7) |
| OF 2010 FBC-RESIDENTIAL. |
| |
| B) IDENTIFY THE ROOF ZONES ON ROUND ROOF ABOVE BEDROOM |
| #3. SEE FIGURE R301.2(7) |
| |
| C) REVISE NAILING SPACING FOR ROOF ZONE #3. NEED TO BE |
| AT 4"O.C. AS REQUIRED BY SEC. R803.2.3.1 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 23- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE |
| DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT |
| FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| |