2013-10-28 17:19:17 | BUILDING PLAN REVIEW |
| PERMIT: 13100748 |
| ADD: 1741 PALM BEACH LAKES BLVD SUITE # E233 |
| CONT: TO BE DETERMINED |
| TEL: (561) |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| |
| 1ST REVIEW |
| DATE: MON. OCT 28/ 2013 |
| ACTION: BUILDING PROVISO: |
| |
| 1) BEFORE PERMIT ISSUANCE!!!! |
| PB OUTLET MALLS: |
| A LETTER FROM THE QUALIFIER OF BOTH THE SHELL |
| CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT |
| CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT |
| PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND |
| NOTARIZED. |
| |
| 2) REVISION REQUIRED, CLEAR PATH OF EGRESS THROUGH BACK |
| OF HOUSE NOT PROVIDED, THE EXIT IS BEHIND THE EXIT |
| ACCESS DOOR. PLEASE SHOW COMPLIANCE WITH: |
| 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES |
| 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. |
| EXCEPTIONS: |
| 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE |
| FOLLOWING ARE MET: |
| |
| 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| THAT FOUND IN THE MAIN RETAIL AREA; |
| |
| 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| THROUGH THE STOCKROOM; |
| |
| 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| EGRESS SIDE; AND |
| |
| 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA |
| TO THE EXIT WITHOUT OBSTRUCTIONS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |