Plan Review Notes
Plan Review Notes For Permit 13100665
Permit Number 13100665
Review Stop E
Sequence Number 1
Notes
Date Text
2013-12-11 20:07:45THE FOLLOWING ITEMS SHALL BE ADDRESSED AND CORRECTED
 ACCORDINGLY:
 1. PAGE E1.0 "SPECIAL PURPOSE OUTLETS" THERE IS A
 CONFLICT ON THE HEATER NOTES. THE NOTES CALL FOR POWER
 SOURCE FROM PANEL PR. THE RISER DIAGRAM REFLECTS TWO
 PANELS, A P AND A R, BUT NO PR.
 2. THE PANEL SCHEDULES FOR EITHER PANELS P OR R DO NOT
 REFLECT ANY HEATER LOAD OR HVAC.
 3. THE ONLY OTHER HEATER IS THE EWH FED FROM THE MDP.
 4. DUE TO ALL THE RE-ARRANGEMENT OF LOADS ON THE
 VARIOUS PANELBOARDS, INDIVIDUAL LOAD CALCS AND A PANEL
 SCHEDULE SHALL BE PROVIDED FOR EACH PANEL.
 5. THE EXISTING RISER MENTIONS "RTU1" W/A 90A
 DISCONNECT. THIS RTU1 DOES NOT APPEAR AGAIN AND NO
 MENTION OF ITS REMOVAL IS MADE.
 6. THE TENANT RISER DIAGRAM REFLECTS AN "EXISTING RTU"
 W/A 70A DISCONNECT AND A "NEW RTU" W/A 60A DISCONNECT.
 AGAIN THERE IS A CONFLICT.
 7. IN AREAS OTHER THAN THOSE DIRECTLY ASSOCIATED WITH
 PATIENT CARE OR THOSE AREAS REQUIRED FOR HEALTH & LIFE
 SAFETY, COMPLIANCE W/THE FBC-ENERGY CONSERVATION IS
 REQUIRED.