Plan Review Notes For Permit 13100452 |
Permit Number |
13100452 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-10-28 17:38:45 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. DESIGN PROFESSIONAL FOR THE RENOVATION SPECIFIES | | BUILDING DESIGN PRESSURE AS 170; NOT CLEAR WHETHER THIS | | APPLIES TO SIGNAGE. SIGN ENGINEERING TO BE REVIEWED BY | | DESIGNER OF RECORD, FBC 1609, OR PROVIDE CLARIFICATION | | LETTER FROM HARTLEY PURDY ARCHITCTURE, OR REVISE | | ENGINEERING DESIGN TO 170MPH EXPOSURE C MINIMUM. | | | | 2. PROPOSED FASTENING NOT CLEAR. THE SECTION ON THE | | LEFT SIDE OF THE PLAN SHOWS (5) 1/4" X 2" TPACONS; 5 | | DOES NOT APPEAR TO BE ENOUGH FASTENERS FOR A 42" X 48" | | M-ARCH SIGN. INSTALL INSTRUCTIONS STATE LAG SCREWS AND | | WASHERS WILL BE USED FOR INSTALLATION; NOT CLEAR FOR | | WHICH OF THE SIGNS THIS APPLIES AND MINIMUM NUMBER OF | | FASTENERS NOT SPECIFIED. | | | | 3. PROVIDE A VERIFIABLE CONTRACT FOR THIS JOB. VALUE IS | | TO INCLUDE LABOR, MATERIALS, AND ENGINEERING, EVEN IF | | THE MATERIALS ARE SUPPLIED BY OTHERS, FBC 109. | | | | | | |
|