Plan Review Notes For Permit 13100420 |
Permit Number |
13100420 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2013-11-01 14:25:44 | REVIEWED NEW REV # 1 SHEETS WITH UNITS ON ROOF OF FIRST | | FLOOR, HUNG OFF OF THE SECOND STORY SIDE WALL, NOTE | | WHEN WITHIN 10'-0" OF THE EDGE OF THE ROOF : | | PROVISO: | | 2010 FBC-B 1013.5 MECHANICAL EQUIPMENT. | | GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, | | FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT | | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF | | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH | | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 | | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD | | SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A | | SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL | | EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END | | OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] |
|