2013-10-21 13:30:19****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH ANCHOR CHARTS. FOR INSTANCE, SEE PAGE 5 OF PANEL
 PRODUCT APPROVAL. NAMING CONVENTION USED IS C1 THROUGH
 C5.
  
 NOTE THAT FOR THE AWNING SHUTTERS, SOME CONNECTION
 TYPES ARE BLOCKED OFF (MEANING THEY CANNOT BE USED WITH
 THAT SPAN, FASTENER, SUBSTRATE).
  
 PLEASE REVISE INSTALLATION SCHEDULE.
  