Plan Review Notes
Plan Review Notes For Permit 13100403
Permit Number 13100403
Review Stop B
Sequence Number 1
Notes
Date Text
2013-11-21 13:02:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DESIGNER TO ELECT A METHOD OF COMPLIANCE, FBC 2010
 EXISTING BUILDING 101.5. AS DESIGNER HAS NOT ELECTED A
 METHOD, COMMENTS WILL REFER TO THE APPLICABLE FBC 2010
 BUILDING REQUIREMENTS (RATHER THAN FBC 2010 EXISTING
 BUILDING). NOTE THAT NOT ENOUGH INFORMATION WAS
 PROVIDED TO GIVE A COMPLETE COMMENT LIST.
  
 2. PROVIDE A BUILDING SUMMARY ? SIZE, BUILDING TYPE,
 OCCUPANCY CLASSIFICATION (FBC CHAPTER 5, 6, 3).
  
 3. INCLUDE OCCUPANCY CLASSIFICATION (FBC CHAPTER 3) AND
 OCCUPANT LOAD OF PROPOSED SPACE, (FBC CHAPTER 10, FBC
 2010 ACCESSIBILITY 201.1.1. IF THIS IS TO BE DESIGNED
 TO BE EXEMPT FROM VERTICAL ACCESSIBILITY REQUIREMENTS,
 CLEARLY INDICATE ON THE PLAN WHICH EXEMPTION THIS FALLS
 UNDER.
  
 4. ILLUMINATION NOT SHOWN BUT IS REQUIRED, FBC 1006.
  
 5. CEILING HEIGHT TO COMPLY WITH FBC 1003.2.
  
 6. BARRIER REQUIRED, FBC 1003.3.1.
  
 7. PROPOSED IMPROVEMENT IS A MEZZANINE, PROVIDE
 INFORMATION SHOWING COMPLIANCE WITH FBC 505.
  
 8. STAIR INFORMATION FBC 1009 NOT SHOWN.
  
 9. HANDRAILS NOT SHOWN FBC 1009.12.
  
 10. PROVIDE A DETAIL WHICH SHOWS COMPLIANCE WITH FBC
 1013.3.
  
  
  