Plan Review Notes For Permit 13100403 |
Permit Number |
13100403 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-11-21 13:02:54 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. DESIGNER TO ELECT A METHOD OF COMPLIANCE, FBC 2010 | | EXISTING BUILDING 101.5. AS DESIGNER HAS NOT ELECTED A | | METHOD, COMMENTS WILL REFER TO THE APPLICABLE FBC 2010 | | BUILDING REQUIREMENTS (RATHER THAN FBC 2010 EXISTING | | BUILDING). NOTE THAT NOT ENOUGH INFORMATION WAS | | PROVIDED TO GIVE A COMPLETE COMMENT LIST. | | | | 2. PROVIDE A BUILDING SUMMARY ? SIZE, BUILDING TYPE, | | OCCUPANCY CLASSIFICATION (FBC CHAPTER 5, 6, 3). | | | | 3. INCLUDE OCCUPANCY CLASSIFICATION (FBC CHAPTER 3) AND | | OCCUPANT LOAD OF PROPOSED SPACE, (FBC CHAPTER 10, FBC | | 2010 ACCESSIBILITY 201.1.1. IF THIS IS TO BE DESIGNED | | TO BE EXEMPT FROM VERTICAL ACCESSIBILITY REQUIREMENTS, | | CLEARLY INDICATE ON THE PLAN WHICH EXEMPTION THIS FALLS | | UNDER. | | | | 4. ILLUMINATION NOT SHOWN BUT IS REQUIRED, FBC 1006. | | | | 5. CEILING HEIGHT TO COMPLY WITH FBC 1003.2. | | | | 6. BARRIER REQUIRED, FBC 1003.3.1. | | | | 7. PROPOSED IMPROVEMENT IS A MEZZANINE, PROVIDE | | INFORMATION SHOWING COMPLIANCE WITH FBC 505. | | | | 8. STAIR INFORMATION FBC 1009 NOT SHOWN. | | | | 9. HANDRAILS NOT SHOWN FBC 1009.12. | | | | 10. PROVIDE A DETAIL WHICH SHOWS COMPLIANCE WITH FBC | | 1013.3. | | | | | | |
|