Plan Review Notes
Plan Review Notes For Permit 13100400
Permit Number 13100400
Review Stop E
Sequence Number 1
Notes
Date Text
2013-10-15 12:43:48THE VAGUE WORDING ON THE SUBMITTED REVISION FORM DOES
 NOT SPECIFY IF THE OUTLETS IN QUESTION ARE THE ONES
 REQUIRED BY NEC 210.63. IF SO, THE ELECTRICAL PLAN
 NOTES BOX LINE ITEM 4 INDICATES THAT THE CIRCUIT FOR
 THESE OUTLETS WILL BE SECURED FROM LP3-37, YET IT IS
 SHOWN ON THE PANEL SCHEDULE FOR LP1S-14. PLEASE HAVE
 THIS CORRECTED FOR THE INSPECTOR IN THE FIELD. BY: MA