2013-10-11 15:55:12RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 FOR NAIL ENHANCING
 AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 OF NOA 13-0204.03 SUBMITTED. NEED THE
 CALCULATIONS TO MEET THE DESIGN PRESSURES OF SEC.
 R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712