Plan Review Notes
Plan Review Notes For Permit 13100374
Permit Number 13100374
Review Stop B
Sequence Number 1
Notes
Date Text
2013-10-23 13:55:59BUILDING PLAN REVIEW
 PERMIT: 13100374
 ADD: 2921 N AUSTRALIAN AVE
 CONT: DBK INDUSTIES
 TEL: (954)581-1994
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: OCT. 23/ 2013
 ACTION: DENIED
  
 1) WITHIN THE DOCUMENTS SUBMITTED ARE A REPAIR LIST
 FROM WPB FIRE DEPARTMENT AND 2 FLOOR PLANS OF THE
 BUILDING. PLEASE IDENTIFY WHERE THESE REPAIRS ARE GOING
 TO BE MADE ON THE FLOOR PLAN.
 NOTE FOR HANDRAILS AND GAURDRAILS SHOP DRAWINGS WILL BE
 REQUIRED AND DESIGNED TO THESE REQUIREMENTS:
 2010 FBC-B:
 HANDRAILS FOR STAIRS & RAMPS 1012.2 HEIGHT.
 HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR
 FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT
 LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38
 INCHES (965 MM). HANDRAIL HEIGHT OF ALTERNATING TREAD
 DEVICES AND SHIP LADDERS, MEASURED ABOVE TREAD NOSINGS,
 SHALL BE UNIFORM, NOT LESS THAN 30 INCHES (762 MM) AND
 NOT MORE THAN 34 INCHES (864 MM).
  
 EXCEPTION: HANDRAILS FOR STAIRS NOT REQUIRED TO BE
 ACCESSIBLE THAT FORM PART OF A GUARDRAIL MAY BE 42
 INCHES (1067 MM) HIGH.
  
 1012.3 HANDRAIL GRASPABILITY.
 ALL REQUIRED HANDRAILS SHALL COMPLY WITH SECTION
 1012.3.1 OR SHALL PROVIDE EQUIVALENT GRASPABILITY.
 EXCEPTIONS: ACCESSIBLE HANDRAILS SHALL MEET THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY.
  
 1012.6 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT OR RAMP RUN. WHERE HANDRAILS ARE
 NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY AT LEAST 12 INCHES (305 MM) BEYOND
 THE TOP RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF
 ONE TREAD BEYOND THE BOTTOM RISER. AT RAMPS WHERE
 HANDRAILS ARE NOT CONTINUOUS BETWEEN RUNS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING
 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF
 RAMP RUNS. THE EXTENSIONS OF HANDRAILS SHALL BE IN THE
 SAME DIRECTION OF THE STAIR FLIGHTS AT STAIRWAYS AND
 THE RAMP RUNS AT RAMPS.
  
 RAMPS 2010 ACCESSIBLITY CODE:
 405.9 EDGE PROTECTION.
 EDGE PROTECTION COMPLYING WITH 405.9.1 OR 405.9.2 SHALL
 BE PROVIDED ON EACH SIDE OF RAMP RUNS AND AT EACH SIDE
 OF RAMP LANDINGS.
 EXCEPTIONS:
 1. EDGE PROTECTION SHALL NOT BE REQUIRED ON RAMPS THAT
 ARE NOT REQUIRED TO HAVE HANDRAILS AND HAVE SIDES
 COMPLYING WITH 406.3.
 2. EDGE PROTECTION SHALL NOT BE REQUIRED ON THE SIDES
 OF RAMP LANDINGS SERVING AN ADJOINING RAMP RUN OR
 STAIRWAY.
 3. EDGE PROTECTION SHALL NOT BE REQUIRED ON THE SIDES
 OF RAMP LANDINGS HAVING A VERTICAL DROP-OFF OF 1/2 INCH
 (13 MM) MAXIMUM WITHIN 10 INCHES (255 MM) HORIZONTALLY
 OF THE MINIMUM LANDING AREA SPECIFIED IN 405.7.
  
 405.9.1 EXTENDED FLOOR OR GROUND SURFACE.
 THE FLOOR OR GROUND SURFACE OF THE RAMP RUN OR LANDING
 SHALL EXTEND 12 INCHES (305 MM) MINIMUM BEYOND THE
 INSIDE FACE OF A HANDRAIL COMPLYING WITH 505.
 ADVISORY 405.9.1 EXTENDED FLOOR OR GROUND SURFACE.
 THE EXTENDED SURFACE PREVENTS WHEELCHAIR CASTERS AND
 CRUTCH TIPS FROM SLIPPING OFF THE RAMP SURFACE.
  
 2) PLEASE INDICATE ON PLANS WHICH INTERIOR NON-BEARING
 WALL IS TO BE DEMOLISHED? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) THE DESIGNER OF THE PLANS IS REQUIRED TO PRINT THEIR
 NAME SIGN THEIR NAME AND LICENSE NUMBER ON THE PLANS.
 107.2.1.3.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  