Plan Review Notes For Permit 13100366 |
Permit Number |
13100366 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-11-06 13:36:13 | THE FOLLOWING ITEMS WERE NOTED AND NEED CORRECTION FOR | | THE ELECTRICAL PLANS REVIEW. | | 1. PAGE CVR MAKES REFERENCE TO NEC 2005 RATHER THAN THE | | 2008 NOW IN EFFECT. | | 2. THE LIGHTING CONTROL DIAGRAM DOES NOT MEET | | FBC-ENERGY CONSERVATION. NO OVER RIDE PROVISIONS | | INDICATED. | | 3. THOUGH THE RISER DIAGRAMS SHOW THE TRANSFORMER, IT | | DOES NOT APPEAR ON THE FLOOR PLANS | | 4. THE ELECTRICAL RISER DIAGRAM SHOWN ON PAGE E@ DOES | | NOT MATCH THE ON SHOWN ON PAGE E3. | | | | PLEASE CORRECT THE ABOVE MENTIONED DEFICIENCIES AND | | RESUBMIT FOR REVIEW. | | | | SENT TO SH DESK |
|