2013-10-17 16:05:51 | 2010 FBC / 2008 NEC | | | | DENIED BY ELECTRIC | | | | 1) SUBMIT TWO SETS OF LOAD CALCULATIONS FOR THE | | EXISTING SERVICE TO SHOW THAT THE PROPOSED 5.6 KW POOL | | HEATER AND POOL EQUIPMENT CAN BE ACCOMMODATED. SPECIFY | | THE SIZE OF THE EXISTING SERVICE AND PROVIDE TWO COPIES | | OF A PANEL SCHEDULE. NEC 220.83 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|