2014-01-07 16:50:59THIS APPLICATION HAS BEEN CONDITIONALLY APPROVED AS
 FOLLOWS:
 1. THE PERMIT APPLICATION HAS TO BE REVISED TO INCLUDE
 ELECTRIC (SUB PERMIT REQUIRED) AS WELL AS TO SIGN ON A
 LICENSED ELECTRICAL CONTRACTOR.
 2. THE SUBMITTED DRAWINGS TO DO NOT INDICATE ANY
 LIGHTING,
 3. THE ERECTION OF THIS WALL NOW CREATES A SEPARATE
 ROOM THEREFORE REQUIRING LIGHTING AT A MINIMUM OF 3
 WATTS PER SQUARE FOOT. THEREFORE IS THERE IS EXISTING
 LIGHTING, IT MAY REMAIN, OTHERWISE ARTIFICIAL LIGHTING
 SHALL BE PROVIDED AS PER FBC AND NEC.
 4. A PANEL SCHEDULE WITH LOAD CALCS HAS NOT BEEN
 PROVIDED, THEREFORE, FOR FINAL INSPECTION, A PROPERLY
 LABELED PANEL AND ACCURATE LOAD CALCS SHALL BE PROVIDED
 TO THE INSPECTOR'S
  
 ALL WORK IS SUBJECT TO THE APPROVAL OF THE FIELD
 INSPECTOR.
  