Plan Review Notes For Permit 13100229 |
Permit Number |
13100229 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-01-07 16:50:59 | THIS APPLICATION HAS BEEN CONDITIONALLY APPROVED AS | | FOLLOWS: | | 1. THE PERMIT APPLICATION HAS TO BE REVISED TO INCLUDE | | ELECTRIC (SUB PERMIT REQUIRED) AS WELL AS TO SIGN ON A | | LICENSED ELECTRICAL CONTRACTOR. | | 2. THE SUBMITTED DRAWINGS TO DO NOT INDICATE ANY | | LIGHTING, | | 3. THE ERECTION OF THIS WALL NOW CREATES A SEPARATE | | ROOM THEREFORE REQUIRING LIGHTING AT A MINIMUM OF 3 | | WATTS PER SQUARE FOOT. THEREFORE IS THERE IS EXISTING | | LIGHTING, IT MAY REMAIN, OTHERWISE ARTIFICIAL LIGHTING | | SHALL BE PROVIDED AS PER FBC AND NEC. | | 4. A PANEL SCHEDULE WITH LOAD CALCS HAS NOT BEEN | | PROVIDED, THEREFORE, FOR FINAL INSPECTION, A PROPERLY | | LABELED PANEL AND ACCURATE LOAD CALCS SHALL BE PROVIDED | | TO THE INSPECTOR'S | | | | ALL WORK IS SUBJECT TO THE APPROVAL OF THE FIELD | | INSPECTOR. | | | | IF YOU HAVE ANY QUESTIONS, FEEL FREE TO CONTACT ME AT | | 561-805-6718 |
|