Plan Review Notes
Plan Review Notes For Permit 13100229
Permit Number 13100229
Review Stop B
Sequence Number 1
Notes
Date Text
2013-10-18 10:38:32BUILDING PLAN REVIEW
 PERMIT:13100229
 ADD: 7100 S DIXIE HWY
 CONT: CILAS CONCRETE
 TEL: (561)689-3427
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY OCT 18/ 2013
 ACTION: DENIED
  
 1) THE PLANS ARE PREPARED BY A DRAFTING SEREVICE AND
 ADVERTISING AS SUCH WITH THERE NAME IN THE TITLEBLOCK.
 F. S. 481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE.
 (C) ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000.00 EXCEPT FOR A SCHOOL, AUDITORIUM OR OTHER
 BUILDING INTENDED FOR PUBLIC USE.
  
 2) PLANS FAIL TO PROVIDE THE LOCATION OF THE WORK TO BE
 COMPLETED UNDER THIS PERMIT, NO SITE PLAN, NO FLOOR
 PLAN WAS PROVIDED INDICATING THE LOCATION THERE ARE TWO
 BUILDINGS ON THIS LOT, AND MORE THAN ONE TENANT SUITE.
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION SECTION
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR BUILDING.
 ASSUMED INTERIOR WALL?
  
 3) OCCUPANT LOAD IS NOT KNOWN OR TRAVEL DISTANCE ? WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 2010 EDITION SECTION
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR BUILDING.
  
 4) THE SUBMITTED PLAN SHOWS EXIT LIGHTS THAT LEAD FOR
 EXITING THROUGH THE STOREROOM EGRESS THROUGH THE
 STORAGE ROOM NOT SHOWN NOR COMPLIANCE WITH;
 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
 EXCEPTIONS:
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
  
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
  
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
  
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
  
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA
 TO THE EXIT WITHOUT OBSTRUCTIONS.
  
 5) IS THIS A CHANGE IN OCCUPANCY? * 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, 2010 EDITION 2012 FBC 107.3.5.1.1
 MINIMUM PLAN REVIEW CRITERIA.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676