Plan Review Notes For Permit 13100177 |
Permit Number |
13100177 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-10-11 11:38:59 | NEED TO COMPLY WITH FBC 1603.1.4 FOR WIND DDSIGN DATA | | ON CONSTRUCTION DOCUMENTS. | | | | 1) PROVIDE ULTIMATE DESIGN WIND SPEED AND NORMAL DESIGN | | WIND SPEED AS DETERMINED IN ACCORDANCE WITH FBC SECTION | | 1609.3.1. | | 2) PROVIDE RISK CATEGORY FROM TABLE 1604.5 OR TABLE | | 1.5-1 OF ASCE 7. | | 3) WIND EXPOSURE. | | 4) APPLICABLE ENCLOSURE CLASSIFICATION. | | 5) COMPONETS AND CLADDING DESIGN PRESSURES. | | | | REVIEWED BY WDS. | | | | DENIED SENT TO (F). | | CALL CONTRACTOR. | | |
|