Plan Review Notes
Plan Review Notes For Permit 13100088
Permit Number 13100088
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-10-07 15:36:14THIS PLAN IS APPROVED WITH COMMENTS.
  
 1. ON PAGE A -5 UNDER SECTION 2, FINISHES, IN THE
 COMMENTS IT STATES " ALL INTERIOR WALL AND CEILING
 FINISHES TO HAVE A MIN CLASS "C" FLAME SPREAD
 CLASSIFICATION. ACCORDING TO NFPA 101 FL ED., CHAPTER
 39; 39..3.3.2.1- INTERIOR WALL AND CEILING FINISH
 MATERILAS COMPLYING WITH SECTION 10.2 SHALL BE CLASS A
 OR B IN EXITS AND IN EXIT ACCESS CORRIDORS.
  
 ACCORDING TO THE PLAN THERE ARE 4 EXIT ACCESS CORRIDORS
 THAT MEET THIS REQUIREMENT. THESE CORRIDORS SHALL HAVE
 A WALL FINISH OF CLASS A OR B. A MATERIAL LIST AND/OR
 PRODUCT SHEET SHALL BE AVAILABLE FOR THE FIRE INSPECTOR
 AT ANY TIME IT IS REQUESTED.
  
 2. EMERGENCY LIGHING IS REQUIRED UNDER NFPA 101 FL ED.,
 CHAPTER 39, 39.2.9.1. PLEASE PROVIDE FOR EMERGENCY
 LIGHTING AS REQUIRED. DUAL SERVICE EXIT/EMERGENCY
 LIGHTS ARE ACCEPTABLE WHERE APPLICABLE. ADDITIONAL
 LIGHTS MAY BE NEEDED ALONG EXIT ACCESS CORRIDORS.
  
 3. AN EXIT LIGHT IS NOT INDICATED AT THE BREAK ROOM
 REAR DOOR. IF ONE IS NOT EXISTING, PLEASE INSTALL ONE
 AT THAT LOCATION. A FIRE INSPECTOR SHALL INSPECT AND
 VERIFY ON INSPECTION.
  