Plan Review Notes For Permit 13100088 |
Permit Number |
13100088 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-10-07 15:36:14 | THIS PLAN IS APPROVED WITH COMMENTS. | | | | 1. ON PAGE A -5 UNDER SECTION 2, FINISHES, IN THE | | COMMENTS IT STATES " ALL INTERIOR WALL AND CEILING | | FINISHES TO HAVE A MIN CLASS "C" FLAME SPREAD | | CLASSIFICATION. ACCORDING TO NFPA 101 FL ED., CHAPTER | | 39; 39..3.3.2.1- INTERIOR WALL AND CEILING FINISH | | MATERILAS COMPLYING WITH SECTION 10.2 SHALL BE CLASS A | | OR B IN EXITS AND IN EXIT ACCESS CORRIDORS. | | | | ACCORDING TO THE PLAN THERE ARE 4 EXIT ACCESS CORRIDORS | | THAT MEET THIS REQUIREMENT. THESE CORRIDORS SHALL HAVE | | A WALL FINISH OF CLASS A OR B. A MATERIAL LIST AND/OR | | PRODUCT SHEET SHALL BE AVAILABLE FOR THE FIRE INSPECTOR | | AT ANY TIME IT IS REQUESTED. | | | | 2. EMERGENCY LIGHING IS REQUIRED UNDER NFPA 101 FL ED., | | CHAPTER 39, 39.2.9.1. PLEASE PROVIDE FOR EMERGENCY | | LIGHTING AS REQUIRED. DUAL SERVICE EXIT/EMERGENCY | | LIGHTS ARE ACCEPTABLE WHERE APPLICABLE. ADDITIONAL | | LIGHTS MAY BE NEEDED ALONG EXIT ACCESS CORRIDORS. | | | | 3. AN EXIT LIGHT IS NOT INDICATED AT THE BREAK ROOM | | REAR DOOR. IF ONE IS NOT EXISTING, PLEASE INSTALL ONE | | AT THAT LOCATION. A FIRE INSPECTOR SHALL INSPECT AND | | VERIFY ON INSPECTION. | | |
|