Plan Review Notes For Permit 13100085 |
Permit Number |
13100085 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-10-08 09:55:22 | DOORS/WINDOWS REPLACEMENT, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- ACCORDING TO SEC. 1609.4.3 THIS BUILDING IS LOCATED | | IN EXPOSURE "D" NOT "C". ENGINEER TO REVISE HIGHLIGHTED | | CALCULATIONS AS REQUIRED. | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR THE SLIDING WINDOWS. | | | | 3- CLARIFY WHY THERE ARE TWO DIFFERENT SLIDING GLASS | | DOORS PRODUCT APPROVALS SUBMITTED. SEC. 107.2.1 CITY | | AMENDMENTS TO FBC. | | | | 4- CLARIFY WHY USING 50SF AS THE TRIBUTARY AREA ON THE | | COMPONENTS AND CLADDING CALCULATIONS. SEC. 107.2.1.3 | | CITY AMENDMENTS TO FBC. | | | | ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|