2013-10-28 16:16:14 | BUILDING PLAN REVIEW |
| PERMIT: 13100069 |
| ADD: 1801 N FLAGLER DR SUITE # 436 |
| CONT: REGIONS PROPERTY MGMT & CONSTRUCTION, INC |
| TEL: (561)292-9881 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MONDAY OCT 28/2013 |
| ACTION: DENIED |
| |
| 1) IT APPEARS THERE MAY BE A DISCREPANCY IN THE PLANS |
| AND PERMIT APPLICATION. THE PERMIT APPLICATION, WITH |
| THE PCN NUMBER 74-43-43-15-39-001-4360 TIES THE WORK TO |
| UNIT 436, ON THE FOURTH FLOOR AND WITHIN THE ACTUAL |
| UNIT. THE PLANS APPEAR TO BE CREATING A NEW STORAGE |
| AREA THAT IS NOT TIED TO THE FOUTH FLOOR SUITE 436. |
| WITH CONDOMINIUMS WORK THAT IS TO BE COMPLETED WITHIN |
| THE COMMON AREAS USE THE TRUNKATED PCN 74-43-43-15-39. |
| PLEASE PROVIDE A SITE PLAN SHOWING THE LOCATION OF THIS |
| NEW STORAGE ROOM, WHAT FLOOR IT IS TO BE LOCATED ON, IF |
| IT FACES THE EXTERIOR, IF THE BACK WALL IS NEW OR IS |
| THE FRONT WALL THE ONLY NEW EXTERIOR WALL. 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 2) 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. THIS IS |
| CREATING NEW STORAGE ROOM, PLEASE PROVIDE COMPLIANCE |
| WITH: 2010 FBC-B SECTION |
| 2.1) 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| FITTING TO THE FRAME AND SILL. |
| |
| 2.2) 1207.2.1 MASONRY. |
| THE SOUND TRANSMISSION CLASS OF CONCRETE MASONRY AND |
| CLAY MASONRY ASSEMBLIES SHALL BE CALCULATED IN |
| ACCORDANCE WITH TMS 0302 OR DETERMINED THROUGH TESTING |
| IN ACCORDANCE WITH ASTM E 90. |
| |
| 2.3) 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 3) THE PLANS DO NOT INDICATE IF THE EXTERIOR DOORS ARE |
| GOING TO REQUIRE A FIRE RESISTANCE RATING, IS THE |
| BUILDING FIRE SPRINKLERED? |
| |
| 4) THE HEIGHT OF THE BUILDING IS ALSO NOT INDICATED, |
| POSITIVE PRESSURES BUILD FROM GRADE, THE NEGATIVE |
| PRESSURES ARE TAKEN FROM THE HEIGHT OF THE BUILDING |
| PLEASE UPDATE PRESSURES, ALSO THE PLANS INDICATE A "C" |
| EXPOSURE, THIS LOCATION IS NEXT TO THE INTERCOASTAL |
| WATER WAY, IS CONSIDERED A "D" EXPOSURE PLEASE UPDATE |
| PRESSURES. |
| 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| |
| 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| |
| 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| |
| 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| |
| 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| TABLE 1609.2(2) . |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |