Notes
Date Text
2013-10-01 17:31:172010 FBC
  
 DENIED BY BUILDING
  
 1) SPECIFY THE APPROVED ASSEMBLY, FASTENING OPTION AND
 MAXIMUM DESIGN PRESSURE FOR THE TAMKO MODIFIED ROOF
 SYSTEM (NOA NO. 12-1003.05) THAT WILL BE USED.
  
 2) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING FOR CORNER AND
 PERIMETER ROOF AREAS AS REQUIRED BY LIMITATION NUMBER 7
 ON PAGE 14 OF THE PRODUCT APPROVAL FOR THE TAMKO
 MODIFIED ROOF SYSTEM (NOA NO. 12-1003.05)
 THE RAS 117 CALCULATIONS THAT WERE SUBMITTED CONTAINS
 ERRORS. THE ROOF HEIGHT IS SPECIFIED AS GREATER THAN 50
 FEET AND THE STRUCTURE IS ONE STORY. INDICATE THE NOA
 PAGE NUMBER AND FASTENING OPTION FOR THE APPROVED
 ASSEMBLY THAT WILL BE USED. THE STRUCTURE IS LOCATED IN
 EXPOSURE CATEGORY "C" AND THE CALCULATIONS SPECIFY "D".
 THE CALCULATION FOR ROOF ZONE 3 (CORNERS) USES 89 PSF
 RATHER THAN 132.6 PSF. THE FASTENER SPACING THAT WAS
 CALCULATED FOR ROOF ZONE 2 IS 5.36 " . THIS SHOULD BE
 ROUNDED DOWN TO 5" NOT INCREASED TO 6" O.C. PLEASE
 CORRECT.
  