2013-10-01 17:31:17 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) SPECIFY THE APPROVED ASSEMBLY, FASTENING OPTION AND | | MAXIMUM DESIGN PRESSURE FOR THE TAMKO MODIFIED ROOF | | SYSTEM (NOA NO. 12-1003.05) THAT WILL BE USED. | | | | 2) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | CALCULATIONS FOR ENHANCED FASTENING FOR CORNER AND | | PERIMETER ROOF AREAS AS REQUIRED BY LIMITATION NUMBER 7 | | ON PAGE 14 OF THE PRODUCT APPROVAL FOR THE TAMKO | | MODIFIED ROOF SYSTEM (NOA NO. 12-1003.05) | | THE RAS 117 CALCULATIONS THAT WERE SUBMITTED CONTAINS | | ERRORS. THE ROOF HEIGHT IS SPECIFIED AS GREATER THAN 50 | | FEET AND THE STRUCTURE IS ONE STORY. INDICATE THE NOA | | PAGE NUMBER AND FASTENING OPTION FOR THE APPROVED | | ASSEMBLY THAT WILL BE USED. THE STRUCTURE IS LOCATED IN | | EXPOSURE CATEGORY "C" AND THE CALCULATIONS SPECIFY "D". | | THE CALCULATION FOR ROOF ZONE 3 (CORNERS) USES 89 PSF | | RATHER THAN 132.6 PSF. THE FASTENER SPACING THAT WAS | | CALCULATED FOR ROOF ZONE 2 IS 5.36 " . THIS SHOULD BE | | ROUNDED DOWN TO 5" NOT INCREASED TO 6" O.C. PLEASE | | CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|