Plan Review Notes
Plan Review Notes For Permit 13090935
Permit Number 13090935
Review Stop B
Sequence Number 2
Notes
Date Text
2013-12-06 06:31:562010 FBC
  
 DENIED BY BUILDING
  
 1) THE VALUE OF $24,150.00 LISTED ON THE APPLICATION
 FOR THE "REVISED" SCOPE OF WORK INDICATED BY THE
 RE-SUBMITTED PLANS TO FABRICATE AND INSTALL (1) NON -
 ILLUMINATED REVERSE CHANNEL LETTER SIGN AND (2)
 ILLUMINATED 20' TALL BLADE SIGNS IS LOW. FOR PERMITTING
 PURPOSES THE VALUATION IS TO INCLUDE ALL DESIGN,
 FABRICATION, INSTALLATION COSTS, OVERHEAD AND PROFIT.
 PLEASE SUBMIT TWO COPIES OF THE SIGNED CONTRACT FOR
 THIS WORK. CITY AMENDMENTS 109.3
  
 2) THE SCOPE OF WORK ON THE APPLICATION WILL NEED TO BE
 CHANGED TO CORRESPOND WITH THE PLANS.
  
 3) THE PLANS INDICATE THAT ONE OF THE BLADE SIGNS IS
 ATTACHED TO THE CORNER OF THE BUILDING. THE ENGINEERING
 ONLY SHOWS A FLAT BRACKET AND AN ANGLE BRACKET WILL BE
 NEEDED TO ATTACH THE SIGN AT THE CORNER. PROVIDE
 ENGINEERING FOR THE BLADE SIGN THAT WILL BE MOUNTED TO
 THE CORNER OF THE BUILDING. FBC 1604.2
  
 NOTE: IN ORDER TO SPEED PLAN REVIEW TIME, PLEASE
 PROVIDE A RESPONSE LETTER INDICATING HOW EACH REVIEW
 COMMENT WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]