2013-10-03 12:41:28BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
  
 1ST REVIEW
 DATE: OCT. 03/2013
 ACTION: DENIED
  
 1) SHEET S.00-01 WIND DESIGN CRITERIA, PLEASE REFER TO
 THE 2010 FBC-B FIGURE 1609A THE BUILDINGS LOCATION IS
 IN A VULT WIND SPEED OF 170 MPH, 3 SECOND GUST OR 132
 MPH VASD 3 SECOND GUST. EXPOSURE "C".
  
 2) NO PRESSURES WERE GIVEN FOR COMPONENTS AND CLADDING.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 2.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 2.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 3) SHEET S01-01 INDICATES THIS PROJECT IS TO BE A
 TILT-WALL SYSTEM, PLEASE SEE REQUIREMENTS FOR A
 RESIDENT INSPECTOR. FBC* 109.3.7 RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE DOCUMENTS TO KEN
 CONRAD MANAGER OF THE RESIDENT INSPECTOR PROGRAM. A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS
 PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQ FT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
 KEN CONRADS CONTACT INFORMATION:
 TEL: 561-805-6715
 E-MAIL: [email protected]
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) NOT REVIEWED UNTIL THE DESIGNER OF RECORD APPLIES
 THEIR SHOP-DRAWING STAMP OF REVIWE.2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, LOUVER REPORT 06-0526.02
 EXPIRED.
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 6) ROOFING APPROVAL NOA 12-0625.02 FIRESTONE TPO
 SUB-SYSTEM PAGE 45 FASTENER OPTION # 5 MAXIMUM PRESSURE
 OF -45 PSF. ENHANCED FASTENING WILL BE REQUIRED IN ROOF
 ZONES 2 & 3 BY A FL. DESIGN PROFESSIONAL. 1609.6.4.4.1.
  
 7) KAWNEER NOA 11-1013.04 STOREFRONT DOORSPLEASE
 INDICATE WHICH DOOR TYPE AND HARDWARE ARE TO BE
 INSTALLED, THE PRESSURES VARY GREATLY.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  