Date Text
2013-12-05 10:18:06BUILDING PLAN REVIEW
 PERMIT: 13090825
 ADD: 1155 BELVEDERE RD
 CONT: TO BE DETERMINED/ FRITZ MASSON
 TEL: (954)710-1118
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURSDAY DEC. 05/ 2013
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) SHEET S1.01 STRUCTURAL DESIN / WIND DESIGN CRITERIA
 THE PLANS HAVE BEEN UPDATED TO THE CORRECT BUILDING
 CATEGORY II WITH ASSOCIATED WIND DESIGN OF 170 MPH, 3
 SECOND GUST BUT THE EXPOSURE HAS CHANGED FROM THE FIRST
 REVIEW EXPOSURE "C" TO A EXPOSURE "B". THE CORRECT
 EXPOSURE IS A "C" EXPOSURE THAT WILL AFFECT THE
 PRESSURES AND PRODUCT APPROVALS. PLEASE REVIEW AND
 UPDATE POSITIVE AND NEGATIVE PRESSURES ACCORDINGLY,
 NOTE THERE IS A MULTIPLIER TO BE USED WITH A "C"
 EXPOSURE.
  
  
  
 2) 2ND REQUEST. UPDATE THE WIND LOAD/ PRESSURE CHART,
 THIS CHART DOES NOT INDICATE IF THE AREA AFFECTED IS 10
 SF, 20, 50, OR 100 SF. NOR HEIGHT ADJUSTMENT FACTORS.
 2010 FBC-B TABLE 1609.
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) PRESSURES WILL BE AFFECTED BY THE C EXPOSURE, AGAIN
 THE COMMENT # 2 WAS NOT ADDRESSED THIS PORTION OF THE
 REVIEW CAN NOT HAPPEN WITH OUT THE PRESSURES BROKE OUT
 TO 10, 20, 50 OR 100 SQ FT. 2 010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 5) COMPLIED..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]