2013-10-19 12:03:28 | BUILDING PLAN REVIEW |
| PERMIT: 13090825 |
| ADD: 1155 BELVEDERE RD |
| CONT: TO BE DETERMINED/ FRITZ MASSON |
| TEL: (954)710-1118 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SATURDAY OCT. 19/ 2013 |
| ACTION: DENIED |
| |
| 1) SHEET S1.01 STRUCTURAL DESIN / WIND DESIGN CRITERIA |
| INDICATES A BUILDING RISK CATEGORY I WITH WIND AT VULT |
| 155 MPH/ 3 SECOND GUST. PLEASE REFER TO THE 2010 FBC-B |
| TABLE 1604.5 RISK CATEGORY I BUILDINGS INCLUDE MINOR |
| STORAGE FACILITIES, SHEDS, AGRICULTURAL FACILITIES & |
| SCREEN ENCLOSURES. PLEASE UPDATE WIND DESIGN CRITEIA |
| AND ASSOCIATED PRESSURES. |
| |
| 1604.5.1 MULTIPLE OCCUPANCIES. |
| WHERE A BUILDING OR STRUCTURE IS OCCUPIED BY TWO OR |
| MORE OCCUPANCIES NOT INCLUDED IN THE SAME RISK |
| CATEGORY, IT SHALL BE ASSIGNED THE CLASSIFICATION OF |
| THE HIGHEST RISK CATEGORY CORRESPONDING TO THE VARIOUS |
| OCCUPANCIES. WHERE BUILDINGS OR STRUCTURES HAVE TWO OR |
| MORE PORTIONS THAT ARE STRUCTURALLY SEPARATED, EACH |
| PORTION SHALL BE SEPARATELY CLASSIFIED. WHERE A |
| SEPARATED PORTION OF A BUILDING OR STRUCTURE PROVIDES |
| REQUIRED ACCESS TO, REQUIRED EGRESS FROM OR SHARES LIFE |
| SAFETY COMPONENTS WITH ANOTHER PORTION HAVING A HIGHER |
| RISK CATEGORY, BOTH PORTIONS SHALL BE ASSIGNED TO THE |
| HIGHER RISK CATEGORY. |
| |
| 2) UPDATE THE WIND LOAD/ PRESSURE CHART, THIS CHART |
| DOES NOT INDICATE IF THE AREA AFFECTED IS 10 SF, 20, |
| 50, OR 100 SF. NOR HEIGHT ADJUSTMENT FACTORS. 2010 |
| FBC-B TABLE 1609. |
| |
| 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 4) 2 010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| 5) SHEET S2.01 DETAIL # 14 TOWER DETAIL INDICATES THE |
| STEEL STUD WALL SECTION BEING TIED DOWN TO THE 2X |
| SOLLID BLOCKING BETWEEN THE JOIST BUT NO TIE DOEN TO |
| THE CONCRETE WALL BENEATH, PART OF THE MWFRT, MAIN WIND |
| FORCE RESISTING SYSSTEM. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |