2013-09-25 08:33:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DESIGN PRESSURES FOR THIS JOB (EXPOSURE C, 15' MRH)
 ARE -36.9, -63.6, AND -95.7 (ZONES 1, 2, AND 3
 RESPECTIVELY).
  
 THE ASSEMBLY SELECTED IS FOR -90PSF AND DOES NOT MEET
 THE MINIMUM REQUIREMENT FOR THE ZONE 3. THE NOTE WHICH
 STATES THAT ENHANCEMENT LETTER IS NOT REQUIRED AS THIS
 IS UNDER 400 SQUARE FEET IS NOT APPLICABLE AS
 COMPLIANCE IS REQUIRED BY FBC 2010 RESIDENTIAL 301.
  
 ENHANCED FASTENING TO BE SPECIFIED BY A DESIGN
 PROFESSIONAL, SEE #8 ON PAGE 2.
  