Plan Review Notes For Permit 13090779 |
Permit Number |
13090779 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-09-25 08:33:55 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. DESIGN PRESSURES FOR THIS JOB (EXPOSURE C, 15' MRH) | | ARE -36.9, -63.6, AND -95.7 (ZONES 1, 2, AND 3 | | RESPECTIVELY). | | | | THE ASSEMBLY SELECTED IS FOR -90PSF AND DOES NOT MEET | | THE MINIMUM REQUIREMENT FOR THE ZONE 3. THE NOTE WHICH | | STATES THAT ENHANCEMENT LETTER IS NOT REQUIRED AS THIS | | IS UNDER 400 SQUARE FEET IS NOT APPLICABLE AS | | COMPLIANCE IS REQUIRED BY FBC 2010 RESIDENTIAL 301. | | | | ENHANCED FASTENING TO BE SPECIFIED BY A DESIGN | | PROFESSIONAL, SEE #8 ON PAGE 2. | | |
|