Plan Review Notes For Permit 13090774 |
Permit Number |
13090774 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-09-25 18:40:42 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. DESIGN PRESSURES APPEAR TOO LOW, PROVIDE | | CALCULATIONS AS TO HOW THESE PRESSURES HAVE BEEN | | DETERMINED. SEE TABLE FBC R 301.2.1.7 TO OBTAIN DESIGN | | PRESSURES. REVISE INSTALLATION SCHEDULE. | | | | 2. UNABLE TO LOCATE ITW TAPCON ON THE ANCHOR CHARTS. | | PLEASE CIRCLE PROPOSED INSTALLATION AND REVISE | | INSTALLATION SCHEDULE. REGULAR TAPCON AND 410 SS TAPCON | | CANNOT BE USED IN DETAIL 1, TOP, TO MASONRY. 410 SS | | TAPCON CANNOT BE USED IN DETAIL 1, BOTTOM, TO MASONRY. | | REVISE INSTALLATION SCHEDULE. | | | | | | | | |
|