2013-11-08 07:06:16REVISION
  
 1) THE FIELD OBSERVATION REPORTS WERE GIVEN TO THE
 CHIEF BUILDING INSPECTOR, KEN CONRAD, FOR HIS REVIEW.
  
 2) THE SIGNED AND SEALED FOUNDATION REPAIR DRAWINGS ARE
 READY FOR PICKUP.
  
 3) THE THREE SHEETS OF PLANS A0, A01 AND A02 THAT WERE
 SUBMITTED ARE DENIED. SEE NOTES BELOW.
  
 2010 FBC
  
 DENIED BY BUILDING
  
 1) SHEET A01 SPECIES DESIGN PARAMETERS BASED ON THE
 2007 FBC AND ASCE 7-08. THIS PERMIT WAS ISSUED UNDER
 THE 2010 FBC AND ASCE 7-10. THE WIND SPEED FOR THE CITY
 OF WEST PALM BEACH FOR A RISK CATEGORY II STRUCTURE IS
 FOR THE 2010 FBC IS 170 MPH VULT / 132 MPH VASD. THE
 WRONG EDITION OF ACI 315 WAS SPECIFIED. THE 2008
 EDITION OF ACI 315 IS REFERENCED BY THE 2010 FBC.
 PLEASE CORRECT.
  
 2) THE REVISED PLANS THAT WERE SUBMITTED ARE FROM A
 DIFFERENT DESIGNER AND HAVE BEEN SIGNED AND SEALED BY A
 DIFFERENT DESIGN PROFESSIONAL. SINCE THE ORIGINAL PLANS
 ARE BEING REPLACED WITH NEW ONES, ALL OF THE
 INFORMATION PROVIDED ON THE ORIGINAL PLANS WILL NEED TO
 BE REPRODUCED ON THE NEW ONES. FS 471 AND FAC 61G15-27
 SHEET A01 GENERAL INFORMATION, CONTAINED THE PROJECT
 DATA, APPLICABLE CODES, SCOPE OF WORK, VICINITY MAP,
 SITE PLAN, ECT.
 SHEET A02 FLOOR PLANS, CONTAINED THE DEMO FLOOR PLAN
 AND PROPOSED FLOOR PLAN WITH THEIR RESPECTIVE SCHEDULES
 AND NOTES.
 SHEET E01 ELECRTICAL PLANS, CONTAINED THE PLUMBING
 PLAN, PLUMBING RISER DIAGRAM, ELECTRICAL PLAN, LOAD
 CALCULATIONS AND ELECTRICAL SYMBOL LEGEND.
 THE TWO NEW SHEETS CONTAINING THE ELEVATIONS SHOULD BE
 ASSIGNED NEW DRAWING NUMBERS SUCH AS A03 AND A04.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]