Plan Review Notes For Permit 13090763 |
Permit Number |
13090763 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-10-17 07:59:02 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) FAC 61G-15-23.002 REQUIRES ALL PLANS, SPECIFICATIONS | | AND REPORTS BEING FILED FOR PUBLIC RECORD TO BE SIGNED | | AND SEALED BY THE ENGINEER. IT ALSO STATES THAT THE | | PROFESSIONAL ENGINEER SHALL SIGN BY HAND THE LICENSEE'S | | HANDWRITTEN SIGNATURE (FACSIMILES ARE NOT ACCEPTABLE). | | THE DOCUMENTS THAT WERE SUBMITTED DO NOT HAVE ORIGINAL | | HAND WRITTEN SIGNATURES. PLEASE SUBMIT ONE SET OF | | DOCUMENTS WITH THE ENGINEER'S ORIGINAL SIGNATURES, DATE | | AND SEAL. | | | | 2) THE BASIS OF DESIGN ON SHEET SK-1 SPECIFIES A WIND | | VELOCITY OF 140 MPH. THE ULTIMATE DESIGN WIND SPEED | | VULT FOR RISK CATEGORY II STRUCTURES LOCATED IN THE | | CITY OF WEST PALM BEACH IS 170 MPH. (VASD IS 132 MPH) | | FBC 1609.1.1 PLEASE REVISE. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|