Plan Review Notes For Permit 13090717 |
Permit Number |
13090717 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-10-09 09:59:52 | PLANS DENIED | | 1) NOTE # 1 AND 9 CONFLICT EACH OTHER ON PAGE M-1.0 | | OF THE PLANS. | | 2) REFER TO SECTION 503.2.44 SHUT OFF DAMPER CONTROLS | | ( FOR FRESH AIR AND EXHAUST ) 2010 FLORIDA ENERGY CODE. | | 3) PROVIDE CHILLED WATER PIPING PLAN ON MECHANICAL | | PLANS | | PER SECTION 107 FBC 2010 | | 4) SEPARATE APPLICATION, PLANS AND PERMIT REQUIRED FOR | | GREASE HOOD , COOLERS AND FIRE SUPPRESSION FOR GREASE | | HOOD . | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|