Plan Review Notes
Plan Review Notes For Permit 13090717
Permit Number 13090717
Review Stop M
Sequence Number 1
Notes
Date Text
2013-10-09 09:59:52PLANS DENIED
 1) NOTE # 1 AND 9 CONFLICT EACH OTHER ON PAGE M-1.0
 OF THE PLANS.
 2) REFER TO SECTION 503.2.44 SHUT OFF DAMPER CONTROLS
 ( FOR FRESH AIR AND EXHAUST ) 2010 FLORIDA ENERGY CODE.
 3) PROVIDE CHILLED WATER PIPING PLAN ON MECHANICAL
 PLANS
 PER SECTION 107 FBC 2010
 4) SEPARATE APPLICATION, PLANS AND PERMIT REQUIRED FOR
 GREASE HOOD , COOLERS AND FIRE SUPPRESSION FOR GREASE
 HOOD .