2013-10-17 09:05:25 | SHEET E1.0 INDICATES #6 ISOLATED GROUND FROM XFORMER | | AND BETWEEN PANELBOARDS. PLEASE INDICATE METHODS OF | | COMPLIANCE WITH 250.30, 250 PART III, 250.58, 250.104, | | PROVIDE STROBES IN BATHROOMS. PLANS NOTED AND APPROVED. | | GIVEN TO J WITMER. |
|