Plan Review Notes
Plan Review Notes For Permit 13090669
Permit Number 13090669
Review Stop E
Sequence Number 2
Notes
Date Text
2013-11-27 12:22:17SENT TO SH DESK
2013-11-27 12:21:28PROVISIOS:
 1. THE SCOPE OF THIS PERMIT IS AS INDICATED ON THE
 PERMIT APPLICATION, TO REMOVE AND REPLACE BROKEN METER
 SOCKET AND RISER PIPE. IF THE REMOVAL OF THE METER
 SOCKET CREATES A SITUATION WHERE THE FEEDERS MUST BE
 REPLACED, THE NEW WIRING, REGARDLESS OF WHAT IS
 EXISTING, SHALL BE IN ACCORDANCE WITH THE CURRENT
 EDITION OF THE NEC.
 2. ALL GROUNDING SYSTEM SHALL BE REPLACED AND MADE
 CURRENT, INCLUDING THE INSTALLATION OF THE INTER-SYSTEM
 BONDING TERMINAL REQUIRED BY NEC 250.94.
 3. ALL WORK SHALL COMPLY WITH ALL REQUIREMENTS OF THE
 2008 EDITION OF THE NEC AND IS SUBJECT TO THE APPROVAL
 OF THE FIELD INSPECTOR.
2013-11-27 11:54:52THE CONTRACTOR CALLED IN THIS MORNING ALLEGING THAT
 DOUG HAD ALREADY SIGNED OFF ON THIS PERMIT, BUT THE
 RECORDS DO NOT REFLECT SUCH. I WILL ONCE AGAIN LOOK AT
 THE SUBMITTAL AND EVALUATE THE CIRCUMSTANCES.