Date |
Text |
2014-02-22 11:14:28 | BUILDING PLAN REVIEW |
| PERMIT: 13090639 |
| ADD: 800 HANK AARON DRIVE BUILDING # 11, MODEL TYPED / |
| 4 STORY, MIZNER LAKES |
| CONT: KAST CONSTRUCTION |
| TEL: (561)324-8082 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2ND REVIEW |
| DATE: SAT. FEB. 22/2014 |
| ACTION: DENIED |
| |
| 1) 1) THIS PERMIT IS FOR BUILDING # 11 A (4) STORY |
| MODEL-TYPE D BUILDING. THE SUBMITTALS INCLUDED A |
| WRITTEN THRESHOLD INSPECTION PLAN WHICH WILL BE |
| REQUIRED FOR ALL (4) STORY BUILDINGS. |
| |
| 2) BUILDINGS THAT ARE GOING TO BE BUILT IN PHASE 2 AS A |
| ADDENDIUM TO THE THRESHOLD DOCUMENTS, PLEASE LIST THEM |
| INTO THE DOCUMENTS FOR THE THRESHOLD & RESIDENT |
| INSPECTOR PACKAGE SO YOU DO NOT HAVE TO GO THROUGH THE |
| PAPERWORK FOR EACH PERMIT. NOTE THRESHOLD DOCUMENTS |
| WILL BE NEEDED FOR BUILDING #11,12,&13 ALL 3 BEING 4 |
| STORY BUILDINGS. THIS COMMENT DEALS WITH THE 4 STORY |
| BUILDINGS: |
| THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS. |
| NOTE: A E-MAIL AND ATTACHMENT WAS SENT TO |
| [email protected] WITH THE GUIDELINES & POLICIES |
| FOR PROJECTS CONCERNING SPECIAL INSPECTORS & RESIDENT |
| INSPECTORS HANDBOOK, FORMS ARE WITHIN THIS DOCUMENT. |
| |
| 2A) COMPLIED. |
| 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| 2B) THRESHOLD INSPECTOR: |
| WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| CODE. |
| CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| BEFORE THE PERMIT MAY BE ISSUED. |
| |
| 2C) COMPLIED. |
| THRESHOLD BLDG, REQUIRED STATEMENT: |
| W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| |
| 2D) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 2D)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| CONRAD: [email protected] |
| |
| 2D)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A |
| RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. |
| THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| 2E) COMPLIED. |
| PLEASE PROVIDE 3 SETS OF PLANS AND ASSOCIATED DOCUMENTS |
| FOR ALL RESIDENT & THRESHOLD BUILDINGS. |
| |
| 3) COMPLIED. |
| SUBMITTED WAS A SINGLE GEOTECHNICAL REPORT BY GFA |
| INTERNATIONAL, AUGUST 19,2013 GFA PROJECT # 13-0924.00, |
| 3 WILL BE REQUIRED. |
| |
| |
| 4A) PLEASE NOTE PRODUCT APPROVALS WERE SUBMITTED, THEY |
| ARE NOT INDICATED AS TO WHICH BUILDING THEY ARE GOING |
| TO BE INSTALLED. WE WILL ASSUME WORST CASE SCENARIO, |
| FOR WALL OPENINGS WE WILL BE LOOKING AT A EXTERIOR |
| CORNER ZONE, ZONE 5, 10 SQ. FT. A ROOF HEIGHT MEAN ROOF |
| HEIGHT FOR THE 4 STORY BUILDING AND A "C" EXPOSURE |
| CATEGORY. THE SAME WILL HOLD TRUE FOR ALL ROOFING |
| PRODUCTS UNLESS THE PRODUCTS ARE BROUGHT IN BUILDING |
| TYPE SPECIFIC, WORST CASE SCENARIO. |
| |
| THE SUBMITTED APPROVALS WILL NOT BE REVIEWED BECAUSE OF |
| TOO MANY UNKNOWNS. |
| |
| 4B) COMPLIED. |
| PLEASE IDENTIFY FOR GLAZED OPENINGS, WINDOWS & DOORS |
| TYPE OF GLAZING, SIZE OF WINDOWS, & ASSOCIATED |
| PRESSURES. 2010 FBC-B 1609.6.4.4.1. COMPONENTS & |
| CLADDING. |
| |
| 4C) 2ND REQUEST, FOR ROOFING APPROVALS, PLEASE IDENTIFY |
| SUB-SYSTEMS AND ASSOCIATED PRESSURES. |
| FOR ROOFING APPROVALS, PLEASE IDENTIFY SUB-SYSTEMS AND |
| ASSOCIATED PRESSURES. |
| SEE IF LIMITATION # 7 OR LIMITATION #9 APPLIES, IF |
| LIMITATION # 7 APPLIES, PLEASE PROVIDE ENHANCED |
| FASTENING AS TO RAS 117. |
| |
| 5) SHEET A501 & A151: |
| |
| 5A) COMPLIED. |
| 5B) FIRE PROTECTION & OPENING PROTECTIVE. |
| PLEASE PROVIDE IN THE BUILDING DATA TABLE IF THE FIRE |
| SPRINKLERS WILL BE NFPA 13 OR 13R? 107.2.1.3. |
| ADDITIONAL INFORMATION IS REQUIRED. |
| PLEASE PROVIDE IN THE BUILDING DATA TABLE IF THE FIRE |
| SPRINKLERS WILL BE NFPA 13 OR 13R? 107.2.1.3. |
| ADDITIONAL INFORMATION IS REQUIRED. |
| PLEASE PROVIDE IN THE BUILDING DATA TABLE IF THE FIRE |
| SPRINKLERS WILL BE NFPA 13 OR 13R? 107.2.1.3. |
| ADDITIONAL INFORMATION IS REQUIRED. THE CODE DATA |
| INDICATES A 13 SYSTEM THE RESPONSE INDICATES A 13R |
| SYSTEM. SHEET FS0.1 INDICATES THE FIRE SPRINKLER SYSTEM |
| TO BE A13R. PLEASE REVIEW PROTECTIVE OPENINGS UNDER |
| TABLE 705.8. UNDER FOOTNOTES: |
| UP, NS = UNPROTECTED OPENINGS IN BUILDINGS NOT EQUIPPED |
| THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 903.3.1.1. |
| UP, S = UNPROTECTED OPENINGS IN BUILDINGS EQUIPPED |
| THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 903.3.1.1. |
| DWELLING UNIT AND SLEEPING UNIT SEPARATIONS IN |
| BUILDINGS OF TYPE IIB, IIIB AND VB CONSTRUCTION SHALL |
| HAVE FIRE-RESISTANCE RATINGS OF NOT LESS THAN 1/2-HOUR |
| IN BUILDINGS EQUIPPED THROUGHOUT WITH AN AUTOMATIC |
| SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1. |
| 903.3.1.1 FULL NFPA 13 SYSTEM. |
| 903.3.1.2 13R SYSTEM. |
| 903.3.1.3 13D SYSTEM. |
| |
| 5C) 2ND REQUEST, |
| FIRE & SMOKE SEPARATION; |
| ) FIRE & SMOKE SEPARATION & LIFE SAFETY LEGEND; THE |
| BUILDING DATA TABLE INDICATES 1/2 HOUR FIRE RATED |
| TENANT SEPARATION WALLS. THE LIFE SAFETY LEGEND |
| INDICATES 709.3 EXCEPTION # 2. DWELLING UNIT AND |
| SLEEPING UNIT SEPARATIONS IN BUILDINGS OF TYPE IIB, |
| IIIB AND VB CONSTRUCTION SHALL HAVE FIRE-RESISTANCE |
| RATINGS OF NOT LESS THAN 1/2-HOUR IN BUILDINGS EQUIPPED |
| THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 903.3.1.1. |
| PLEASE SEE THE EXCEPTION CAN NOT BE TAKEN FOR A 13R |
| SYSTEM. SEE SHEET FS0.1. |
| 903.3.1.1 FULL NFPA 13 SYSTEM. |
| 903.3.1.2 13R SYSTEM. |
| 903.3.1.3 13D SYSTEM. |
| |
| 5D) S PLEASE PROVIDE HOW THIS FIRE RATING WILL CONTINUE |
| OUT INTO THE OVERHANG. |
| 2010 FBC-B 709.4 CONTINUITY, 709.4.1 ROOF CONSTRUCTION, |
| 709.4.1.1 ROOF SHEATHING AND 709.4.1.2 ROOF PROTECTION. |
| |
| 5E) BUILDING DATA TABLE UNDER THE HEADING FIRE |
| PROTECTION & OPENING PROTECTION THE ELEVATOR SHAFT |
| INDICATES REQUIRED AND INCLUDED BUT DOES NOT STATE THE |
| RATING OF THE SHAFT, FBC-B 708.4 |
| REQUIRES 2 HR. |
| |
| 5F) THE HEADING IN THE SAME TABLE FOR VERTICAL SHAFTS |
| INDICATES 1 HOUR SEE FBC-B 708.4. |
| |
| 6) THE PLANS ARE MISSING, |
| 107.3.51.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| BUILDINGS: |
| 6A) COMPLIED. INTERIOR REQUIREMENTS SHALL INCLUDE THE |
| FOLLOWING: |
| INTERIOR FINISHES (FLAME SPREAD & SMOKE DEVELOPMENT) |
| 803.9 & TABLE 803.9. |
| |
| 6B) 2ND REQUEST. SHEET A751 WALL TYPES 4 & 5 NOW STATE |
| TO MEET THE STC 50 REQUIREMENT, BUT THE UL WALL TYPE |
| IDENTIFIED WERE NEVER TESTED TO MEET THE STC RATINGS. |
| THE CODE REQUIREMENT REQUIRES TESTING. |
| |
| 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| FITTING TO THE FRAME AND SILL. |
| |
| C) ) 2ND REQUEST. SHEET A751 WALL TYPES 4 & 5 NOW STATE |
| TO MEET THE STC 50 REQUIREMENT, BUT THE UL WALL TYPE |
| IDENTIFIED WERE NEVER TESTED TO MEET THE STC RATINGS. |
| THE CODE REQUIREMENT REQUIRES TESTING. |
| 1207.2.1 MASONRY. |
| THE SOUND TRANSMISSION CLASS OF CONCRETE MASONRY AND |
| CLAY MASONRY ASSEMBLIES SHALL BE CALCULATED IN |
| ACCORDANCE WITH TMS 0302 OR DETERMINED THROUGH TESTING |
| IN ACCORDANCE WITH ASTM E 90. |
| |
| D) 2ND REQUEST, PROVIDE TESTING REPORT. |
| 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 6E) 2ND REQUEST, THE 20 INCH X 30 INCH OPENING REQUIRED |
| FOR EVERY UNIT WITH ATTIC SPACE IS FOR FIGHTING FIRES |
| WITHIN THE ATTIC SPACE OF THE UNIT, AND FOR INSPECTION |
| PURPOSES. THE RESPONSE INDICATES THE USE OF A 30 INCH X |
| 36 INCH OPENING ON THE ROOF TOP, YOU CAN ONLY GET INTO |
| ONE SPACE SINCE THE TENANT SEPARATION WALLS GO REQUIRE |
| CONTINUITY TO THE ROOF DECK. |
| 2010 FBC-C 1209.2 ATTIC SPACES.AN OPENING NOT LESS THAN |
| 20 INCHES BY 30 INCHES (559 MM BY 762 MM) SHALL BE |
| PROVIDED TO ANY ATTIC AREA HAVING A CLEAR HEIGHT OF |
| OVER 30 INCHES (762 MM). A 30-INCH (762 MM) MINIMUM |
| CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT |
| OR ABOVE THE ACCESS OPENING. |
| |
| 7-9) COMPLIED. |
| |
| 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 11) THE VALUE FOR YOUR PERMIT IS LOW, OUR CALCULATED |
| VALUE IS $5,967,131.00 DOLLARS IN VALUE. |
| W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS |
| REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH ADESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |