2013-10-08 15:57:11 
 ***PROVISO***
 1. A DOMESTIC WATER PUMP/S MAY BE REQUIRED. REQUIRED
 MINIMUM FLOW PRESSURE AT TOP FLOOR IS 20 PSI AT PEAK
 DEMAND.
 FBC PLUMBING 2010 TABLE 604.3
 WATER DISTRIBUTION SYSTEM DESIGN CRITERIA
 REQUIRED CAPACITY AT FIXTURE SUPPLY PIPE OUTLETS
  
 2. FBC PLUMBING 301.6
 ELEVATOR SUMP PUMPS ARE REQUIRED TO BE INDIRECTLY
 CONNECTED TO THE SANITARY.
 FBC 1003.4
 AN OIL SEPARATOR WILL NOT BE REQUIRED IN HYDRAULIC
 ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM IS
 INSTALLED
  
  
  