2013-10-19 09:53:13PLAN DENIED
 1) CONDENSERS ON ROOF. REFER TO SECTION 304.11
 GUARDS 2010 FBC (M). PLAN SHOWS PARAPET IF
 PARAPET MEATS THE REQUIREMENTS OF SECTION 314.11
 GUARDS ARE NOT REQUIRED.
 2) PAGE A 302 DOOR FRAME SCHEDULE SHOW WOOD
 DOORS ON AIR HANDLER CLOSET. REFER TO SECTION
 602.2.1 MATERIALS WITHIN PLENUM'S 2010 FBC (M)
 3) CURB DETAIL # 6 ON PAGE A 250 SHOW A WOOD DECK.
 CURB DETAIL ON PAGE M7.1 SHOW CONCRETE .PLEASE CLARIFY
 PROVIDE A DETAIL FROM THE ENGINEER ON THE CONDENSER
 STAND TO ROOF TIEDOWN AND CONDENSER TO STAND TIEDOWN.
 4) PROVIDE ENERGY CALCULATIONS WITH PLANS. PER SECTION
 503.2.1 FLORIDA ENERGY CODE.