2013-12-17 14:41:43 | THE INTENT OF THIS REVIEW IS NOT TO GENERATE A PUNCH |
| LIST FOR THE DESIGN PROFESSIONAL, BUT ON THE FIRST |
| REVIEW THE FOLLOWING DEFICIENCIES WERE NOTED: |
| 1. PAGE E2.1 |
| A) AS PER NEC 110.26(D), ILLUMINATION IS REQUIRED FOR |
| THE ELECTRICAL ROOMS AS WELL AS FOR THE FIRE RISER |
| CLOSET. |
| 2. PAGE 2.2 & 2.3 |
| A) THE EXIT SIGN DO NOT INDICATE THAT THEY ARE VISIBLE |
| FROM BOTH SIDES. |
| 3. PAGE E4.1 TYPICAL UNIT LIGHTING PLAN |
| A. UNIT A: |
| 1. AS PER NEC 210.70(A)(1), THERE SHALL BE A LIGHT IN |
| THE BALCONY |
| 2. AS PER NEC 110.26(D), THERE SHALL BE ILLUMINATION IN |
| FRONT OF THE ELECTRICAL PANEL |
| B. UNIT B |
| 1. AS PER NEC 210.70(A)(1), RE SHALL BE A LIGHT IN THE |
| BALCONY |
| 2. I SUGGEST THAT FOR BOTH, ENERGY CONSERVATION AS WELL |
| AS CONVENIENCE THAT 3 WAY SWITCHING BE PROVIDED FOR THE |
| LIVING ROOM. |
| C. UNIT C |
| 1. AS PER NEC 210.70(A)(1), RE SHALL BE A LIGHT IN THE |
| BALCONY |
| 2. I SUGGEST THAT FOR BOTH, ENERGY CONSERVATION AS WELL |
| AS CONVENIENCE THAT 3 WAY SWITCHING BE PROVIDED FOR THE |
| LIVING ROOM & CORRIDOR |
| 4. PAGE 4.2 TYPICAL UNIT POWER PLAN |
| A. INDICATE THE SCALE USED FOR THESE DRAWINGS. WITHOUT |
| A SCALE DESIGNATION, PROPER RECEPTACLE AND SMOKE |
| DETECTOR PLACEMENT IS NOT VERIFIABLE. |
| B. NOT THAT IT IS INCORRECT OR IMPROPER, BUT WITH |
| PROPER PLACEMENT THERE IS AN UNREQUIRED SMOKE DETECTOR |
| IN UNITS A & C. |
| C. RELOCATE THE SMOKE DETECTOR OF UNIT B TO THE BEDROOM |
| CORRIDOR |
| D. NEC 406.11 REQUIRES ?TAMPER-RESISTANT ? RECEPTACLES |
| IN DWELLING UNITS |
| 5. PAGE 6.1 PANEL SCHEDULES |
| A. MUST PROVIDE VOLTAGE DROP CALCULATIONS FOR FEEDERS |
| B. AS PER NEC 210.12 ARC-FAULT CIRCUIT INTERRUPTION IS |
| REQUIRED IN DWELLING UNITS. |
| |
| THOUGH A SEPARATE FIRE ALARM PERMIT SHALL BE REQUIRED |
| AND THE NECCESSARY DOCUMENTATION FOR SAME SHALL |
| ACCOMPANY SUCH PERMIT, A PRELIMINARY REVIEW OF THE |
| PLACEMENT OF THE INITIATING DEVICES ON THE SECOND & |
| THIRD FLOOR SHOULD BE RELOCATED TO COMPLY WITH NFPA 72 |
| SECTION 17.14.6 |
| |
| IF YOU HAVE ANY QUESTIONS WITH REGARDS TO ANY OF THESE |
| COMMENTS, PLEASE DO NOT HESITATE TO CONTACT ME. |
| MIKE ALBARRAN, ELECTRICAL PLANS REVIEWER (561) 805-6718 |
| |