2014-01-02 15:29:00 | THE INTENT OF THIS REVIEW IS NOT TO GENERATE A PUNCH |
| LIST FOR THE DESIGN PROFESSIONAL, BUT ON THE FIRST |
| REVIEW THE FOLLOWING DEFICIENCIES WERE NOTED: |
| 1 PAGE E2.1 |
| A. AS PER NEC 110.26(D), ILLUMINATION IS REQUIRED FOR |
| THE ELECTRICAL ROOMS AS WELL AS FOR THE FIRE RISER |
| CLOSET. |
| 2. PAGE 2.2 & 2.3 |
| 3. PAGE 3.1 ALL OUTLETS IN RESIDENTIAL COMMON AREAS |
| SHOULD BE "TAMPER RESISTANT" AS WELL |
| A. THE EXIT SIGN DO NOT INDICATE THAT THEY ARE VISIBLE |
| FROM BOTH SIDES. AS PER NEC 110.26(D), THE METER ROOM |
| HAS TO HAVE ILLUMINATION. THERE SHALL BE ILLUMINATION |
| INSIDE THE OTHER CLOSETS WHICH HAVE EQUIPMENT, AND IN |
| THE FIRE RISER AND STORAGE CLOSETS. |
| 4. PAGE E4.1 TYPICAL UNIT LIGHTING PLAN ALL CEILING FAN |
| BOXES SHALL BE RATED FOR 50#'S AS PER NEC 314.27(A) |
| A. UNIT A: |
| 1. AS PER NEC 210.70(A)(1), THERE SHALL BE A LIGHT IN |
| THE BALCONY |
| 2. AS PER NEC 110.26(D), THERE SHALL BE ILLUMINATION IN |
| FRONT OF THE ELECTRICAL PANEL |
| B. UNIT C: |
| 1. AS PER NEC 210.70(A)(1), THERE SHALL BE A LIGHT IN |
| THE BALCONY |
| 2. THERE SHOULD BE A 3 WAY SWITCH FOR THE CORRIDOR |
| C. UNIT D: |
| 1. AS PER NEC 210.70(A)(1), RE SHALL BE A LIGHT IN THE |
| BALCONY |
| 2. MISSING LIGHT SWITCH FOR M. BATH. |
| 5.. PAGE 4.2 OUTLET PLACEMENT SHALL BE IN ACCORDANCE TO |
| NEC 210.52. |
| B. NOT THAT IT IS NOT INCORRECT OR IMPROPER, BUT WITH |
| PROPER PLACEMENT THERE IS AN UNREQUIRED SMOKE DETECTOR |
| IN EACH UNIT. |
| 6. PAGE 6.1 PANEL SCHEDULES |
| A. MUST PROVIDE VOLTAGE DROP CALCULATIONS FOR FEEDERS |
| |
| |
| THOUGH A SEPARATE FIRE ALARM PERMIT SHALL BE REQUIRED |
| AND THE NECESSARY DOCUMENTATION FOR SAME SHALL |
| ACCOMPANY SUCH PERMIT, A PRELIMINARY REVIEW OF THE |
| PLACEMENT OF THE INITIATING DEVICES ON THE SECOND & |
| THIRD FLOOR SHOULD BE RELOCATED TO COMPLY WITH NFPA 72 |
| SECTION 17.14.6 |
| |
| IF YOU HAVE ANY QUESTIONS WITH REGARDS TO ANY OF THESE |
| COMMENTS, PLEASE DO NOT HESITATE TO CONTACT ME. |
| MIKE ALBARRAN, ELECTRICAL PLANS REVIEWER (561) 805-6718 |
| |