2014-03-04 11:22:24PASS PROVISO
 1) SOME DUCT IS MARKED WITH 25 CFM.
 REVISE FLEX SCHEDULE ON PAGE M6.1
 TO INCLUDE DUCT SIZE FOR 25 CFM.
 2) DETAIL #6 PAGE M7.1 PROVIDE
 THE SIZE OF CONCRETE ANCHOR USED.
 3) DETAIL #3 PAGE M7.2 PROVIDE
 THE SIZE ANCHOR USED ON THE PLAN.
 HAVE REVISION COMPLETED BY 1ST INSPECTION.