2013-12-09 16:26:13 | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR A SUCCESSFUL |
| ELECTRICAL REVIEW AS WELL AS FOR A FIRE ALARM REVIEW. |
| |
| PAGE E4.1, UNIT A2 |
| 1. MISSING THE REQUIRED LIGHT & SWITCH FOR THE BALCONY |
| AS PER NEC 210.70 |
| |
| UNIT TH, 1ST FLOOR |
| 1. AD A 3 WAY SWITCH TO EXTINGUISH LIGHTING AS YOU |
| ENTER THE STAIRS |
| 2. MISSING THE REQUIRED LIGHT & SWITCH FOR THE BALCONY |
| AS PER NEC 210.70 |
| |
| UNIT TH, 2ND FLOOR |
| 1. MISSING LIGHT & SWITCH FOR CORRIDOR. |
| |
| UNIT E |
| 1. MISSING LIGHT SWITCH ADJACENT TO ENTRY DOOR. |
| 2. MISSING THE REQUIRED LIGHT & SWITCH FOR THE BALCONY |
| AS PER NEC 210.70 |
| 3. RELOCATE LIGHT SWITCH TOWARDS ENTRY DOOR OF MASTER |
| BEDROOM |
| |
| UNIT E1 |
| 1. RELOCATE LIGHT SWITCH TOWARDS ENTRY DOOR OF MASTER |
| BEDROOM |
| |
| UNIT E2 |
| 1. RELOCATE LIGHT SWITCH TOWARDS ENTRY DOOR OF MASTER |
| BEDROOM |
| 2. MISSING THE REQUIRED LIGHT & SWITCH FOR THE BALCONY |
| AS PER NEC 210.70 |
| |
| PAGE 4.2, UNIT A2 |
| 1. AS PER NEC 210.52(D)(3), THERE HAS TO BE AN OUTLET |
| ON THE BALCONY |
| |
| UNIT E |
| 1. LINEAR WALL SPACE IN THE LIVING ROOM REQUIRES AN |
| ADDITIONAL OUTLET AS PER NEC 210.52 |
| |
| UNIT TH 1ST FLOOR |
| 1. AS PER NEC 210.52, AN OUTLET IS MISSING IN THE >2' |
| AREA BEHIND THE ENTRY DOOR. |
| 2. RELOCATE THE OUTLETS TO CORRECT SPACING REQUIREMENTS |
| OF NEC 210.52 |
| |
| UNIT E1 & E2 |
| 1. LINEAR WALL SPACE IN THE LIVING ROOM REQUIRES AN |
| ADDITIONAL OUTLET AS PER NEC 210.52 |
| |
| PAGE E6.1 |
| THOUGH PERMITTED BY CODE, IT IS MY OPINION THAT IN THE |
| INTEREST OF LIFE SAFETY THE SMOKE DETECTORS BE |
| CONNECTED TO A GENERAL LIGHTING CIRCUIT TO MAKE IT |
| OBVIOUS OF A TRIPPED BREAKER UNLESS THE DEVICES HAS A |
| MAIN POWER FAILURE WARNING SIGNAL |
| |
| PAGE FA2.1 |
| 1. INTERIOR FIRE WARNING DEVICE IS MISSING FROM INSIDE |
| THE SECOND BEDROOM OF UNIT E |
| |
| |