Plan Review Notes
Plan Review Notes For Permit 13090635
Permit Number 13090635
Review Stop E
Sequence Number 1
Notes
Date Text
2013-12-09 16:26:13THE FOLLOWING CORRECTIONS ARE REQUIRED FOR A SUCCESSFUL
 ELECTRICAL REVIEW AS WELL AS FOR A FIRE ALARM REVIEW.
  
 PAGE E4.1, UNIT A2
 1. MISSING THE REQUIRED LIGHT & SWITCH FOR THE BALCONY
 AS PER NEC 210.70
  
 UNIT TH, 1ST FLOOR
 1. AD A 3 WAY SWITCH TO EXTINGUISH LIGHTING AS YOU
 ENTER THE STAIRS
 2. MISSING THE REQUIRED LIGHT & SWITCH FOR THE BALCONY
 AS PER NEC 210.70
  
 UNIT TH, 2ND FLOOR
 1. MISSING LIGHT & SWITCH FOR CORRIDOR.
  
 UNIT E
 1. MISSING LIGHT SWITCH ADJACENT TO ENTRY DOOR.
 2. MISSING THE REQUIRED LIGHT & SWITCH FOR THE BALCONY
 AS PER NEC 210.70
 3. RELOCATE LIGHT SWITCH TOWARDS ENTRY DOOR OF MASTER
 BEDROOM
  
 UNIT E1
 1. RELOCATE LIGHT SWITCH TOWARDS ENTRY DOOR OF MASTER
 BEDROOM
  
 UNIT E2
 1. RELOCATE LIGHT SWITCH TOWARDS ENTRY DOOR OF MASTER
 BEDROOM
 2. MISSING THE REQUIRED LIGHT & SWITCH FOR THE BALCONY
 AS PER NEC 210.70
  
 PAGE 4.2, UNIT A2
 1. AS PER NEC 210.52(D)(3), THERE HAS TO BE AN OUTLET
 ON THE BALCONY
  
 UNIT E
 1. LINEAR WALL SPACE IN THE LIVING ROOM REQUIRES AN
 ADDITIONAL OUTLET AS PER NEC 210.52
  
 UNIT TH 1ST FLOOR
 1. AS PER NEC 210.52, AN OUTLET IS MISSING IN THE >2'
 AREA BEHIND THE ENTRY DOOR.
 2. RELOCATE THE OUTLETS TO CORRECT SPACING REQUIREMENTS
 OF NEC 210.52
  
 UNIT E1 & E2
 1. LINEAR WALL SPACE IN THE LIVING ROOM REQUIRES AN
 ADDITIONAL OUTLET AS PER NEC 210.52
  
 PAGE E6.1
 THOUGH PERMITTED BY CODE, IT IS MY OPINION THAT IN THE
 INTEREST OF LIFE SAFETY THE SMOKE DETECTORS BE
 CONNECTED TO A GENERAL LIGHTING CIRCUIT TO MAKE IT
 OBVIOUS OF A TRIPPED BREAKER UNLESS THE DEVICES HAS A
 MAIN POWER FAILURE WARNING SIGNAL
  
 PAGE FA2.1
 1. INTERIOR FIRE WARNING DEVICE IS MISSING FROM INSIDE
 THE SECOND BEDROOM OF UNIT E
  
  