2014-05-01 14:27:02FUEL GAS PLAN REVIEW
 PERMIT: 13090634
 ADD: 800 HANK AARON DRIVE / MIZNER LAKES
 SITE AMENITIES: 1) POOL RESTROOMS, 2) TOWER FEATURE &
 3) GATE HOUSE 4) DUMPSTER ENCLOSURE & 5) MAIL KIOSK
 CONT: KAST CONSTRUCTION
 TEL: (561)324-8082
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE:THURS. MAY 01/ 2014
 ACTION: DENIED
  
 GAS IS UNDER A SEPARATE PERMIT, IT MAY BE SHOWN UNDER
 THE SITE AMENITIES PERMIT BUT THE SITE AMENITIES PERMIT
 WILL NOT BE ISSUED UNTIL ALL REQUIREMENTS CAN BE MET
 FOR CODE COMPLIANCE.
  
 1) SHEET P3.1 SHOWS A GAS PLAN FOR THE FIRST TIME,
 COMMENT ON THE GAS PLAN INDICATES SEE SHEET P1.2 FOR
 CONTINUATION, PLEASE NOTE NO SUCH SHEET WAS SUBMITTED
 FOR REVIEW.
  
 2) SHEET P2.1 WAS SUBMITTED WITH A REV.# 2 CLOUDED, IF
 THERE IS TO BE A GAS LINE WITHIN THE CLOUD, IT WAS
 NEVER DRAWN, OR LAYER TURNED ON TO INDICATE A NEW GAS
 LINE.
  
 3)REQUIREMENTS FOR GAS PLAN REVIEW. SUBMIT MANUFACTURE
 SHEETS FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2010 FUEL GAS SEC.
 402.2
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  