Plan Review Notes
Plan Review Notes For Permit 13090634
Permit Number 13090634
Review Stop B
Sequence Number 1
Notes
Date Text
2013-11-02 15:33:40BUILDING PLAN REVIEW
 PERMIT: 13090634
 ADD: 800 HANK AARON DRIVE / MIZNER LAKES
 SITE AMENITIES: 1) POOL RESTROOMS, 2) TOWER FEATURE &
 3) GATE HOUSE 4) DUMPSTER ENCLOSURE & 5) MAIL KIOSK
 CONT: KAST CONSTRUCTION
 TEL: (561)324-8082
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SAT. NOV. 02/ 2013
 ACTION: DENIED
  
 1) THIS PERMIT IS INCLUDES SITE AMENITIES: 1) POOL
 RESTROOMS, 2) TOWER FEATURE & 3) GATE HOUSE, 4)
 DUMPSTER ENCLOSURE & 5) MAIL KIOSK. CLUBHOUSE UNDER A
 SEPARATE PERMIT AS WELL AS POOL & DECK.
  
 2) WITHIN THE SUBMITTED SOILS REPORT BASED ON THE
 RESULTS, LOOSE SOILS AND SOFT ORGANIC SOIL (MUCK) LAYER
 WAS FOUND. THE PLANS DO NOT INDICATE WHICH OF THE THREE
 OPTIONS WERE PICKED FOR THIS PROJECT, THIS MAY AFFECT
 THE TYPE OF FOUNDATION. PLEASE PROVIDE ADDITIONAL
 INFORMATION. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
 A SEPARATE PERMIT WILL BE REQUIRED FOR SOILS WORK.
  
 3) OMITTED.
  
 4A) PLEASE NOTE PRODUCT APPROVALS WERE SUBMITTED, THEY
 ARE NOT INDICATED AS TO WHICH BUILDING THEY ARE GOING
 TO BE INSTALLED. WE WILL ASSUME WORST CASE SCENARIO,
 FOR WALL OPENINGS WE WILL BE LOOKING AT A EXTERIOR
 CORNER ZONE, ZONE 5, 10 SQ. FT. A ROOF HEIGHT MEAN ROOF
 HEIGHT FOR THE 4 STORY BUILDING AND A ?C? EXPOSURE
 CATEGORY. THE SAME WILL HOLD TRUE FOR ALL ROOFING
 PRODUCTS UNLESS THE PRODUCTS ARE BROUGHT IN BUILDING
 TYPE SPECIFIC, WORST CASE SCENARIO.
 THE SUBMITTED APPROVALS WILL NOT BE REVIEWED BECAUSE OF
 TOO MANY UNKNOWNS.
 4B) PLEASE IDENTIFY FOR GLAZED OPENINGS, WINDOWS &
 DOORS TYPE OF GLAZING, SIZE OF WINDOWS, & ASSOCIATED
 PRESSURES. 2010 FBC-B 1609.6.4.4.1. COMPONENTS &
 CLADDING.
 4C) FOR ROOFING APPROVALS, PLEASE IDENTIFY SUB-SYSTEMS
 AND ASSOCIATED PRESSURES.
 SEE IF LIMITATION # 7 OR LIMITATION #9 APPLIES, IF
 LIMITATION # 7 APPLIES, PLEASE PROVIDE ENHANCED
 FASTENING AS TO RAS 117.
  
 5) SHEET A002 BUILDING DATA SHEET DECLARES THE BUILDING
 TYPE FOR THE 3 & 4 STORY R-2 APARTMENT BUILDINGS BUT
 NOT THE SITE AMENITIES.,
  
 6) SHEET A102 SHOW ACCESSIBLE ROUTE INTO THE GATE/
 GUARD HOUSE. 2010 FL ACCESSIBILITY 206.2.2 ACCESSIBLE
 ROUTE WITHIN THE SITE AND TO BUILDINGS.
  
 7) 2010 FBC-C 1209.2 ATTIC SPACES. NONE OF THE A SHEETS
 SHOW ACCESS TO EITHER THE ATTIC SPACE IN THE GATE HOUSE
 OR POOL RESTROOMS. AN OPENING NOT LESS THAN 20 INCHES
 BY 30 INCHES (559 MM BY 762 MM) SHALL BE PROVIDED TO
 ANY ATTIC AREA HAVING A CLEAR HEIGHT OF OVER 30 INCHES
 (762 MM). A 30-INCH (762 MM) MINIMUM CLEAR HEADROOM IN
 THE ATTIC SPACE SHALL BE PROVIDED AT OR ABOVE THE
 ACCESS OPENING.
  
 8) SHEET A104 & A105 BOTH INDICATE THE USE OF DROPPED
 CEILINGS IN BOTH THE GATE HOUSE & POOL RESTROOMS PLANS
 INDICATE 5/8? DRYWALL AS A FINISH BUT THE HORIZONTAL
 FRAMING MEMBERS ARE NOT INDICATED AS TO MATERIAL, SIZE,
 SPACING OR ATTACHMENT TO THE CMU CONSTRUCTION NOR
 SPANS. 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS.
  
 9) SHEET S6 PLYWOOD SHEATHING NOTE D & E INDICATE SEE
 FRAMING PLAN FOR TYPE AND SIZE OF NAILS, WHERE, PROVIDE
 FOR ROOF SHEATHING ZONES 1, 2 & 3. PLEASE PROVIDE
 NAILING FOR THE APPROPRIATE WIND EXPOSURE AND HEIGHT
 FACTORS FOR THIS BUILDING. 107.3.5.1.1 MINIMUM PLAN
 REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. PART OF THE
 MWFRS, MAIN WIND FORCE RESISTING SYSTEM.
  
 10) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10. 1609.3 BASIC WIND SPEED FIGURE
 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
 5) COMPONENTS & CLADDING PRESSURES POSITIVE & NEGATIVE
 TABLE 1609.2(2) .PROVIDE PRESSURES FOR ZONES 1-5.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  