2013-09-28 10:50:314105 MILLER AVENUE
 PERMIT #13090565
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXIT DOORS, EXIT
 SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON
 PATH OF TRAVEL ETC.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL BE APPROPRIATE FOR HAZARD BEING PROTECTED AND
 SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT
 EXCEED 75 FEET.
  
 DESIGN SHALL CONFORM TO NFPA 1 (2009 EDITION) CHAPTER
 52 - STATIONARY STORAGE BATTERY SYSTEMS. SOME OF THE
 REQUIREMENTS ARE INDICATED BELOW:
  
 52.3.10 SMOKE DETECTION. AN APPROVED AUTOMATIC SMOKE
 DETECTION SYSTEM SHALL BE INSTALLED IN SUCH AREAS AND
 SUPERVISED BY AN APPROVED CENTRAL, PROPRIETARY, OR
 REMOTE STATION SERVICE OR A LOCAL ALARM THAT WILL GIVE
 AN AUDIBLE SIGNAL AT A CONSTANTLY ATTENDED LOCATION.
  
 52.3.8.1 DOORS OR ACCESSES INTO ROOMS, BUILDINGS, OR
 AREAS CONTAINING STATIONARY STORAGE BATTERY SYSTEMS
 SHALL BE PROVIDED WITH APPROVED SIGNS. THE SIGNS SHALL
 STATE THAT THE ROOM CONTAINS STATIONARY STORAGE BATTERY
 SYSTEMS, THAT THE BATTERY ROOM CONTAINS ENERGIZED
 ELECTRICAL CIRCUITS, AND THAT THE BATTERY ELECTROLYTE,
 WHERE PRESENT, ARE CORROSIVE LIQUIDS. BATTERY CABINETS
 SHALL BE PROVIDED WITH EXTERIOR LABELS THAT IDENTIFY
 THE MANUFACTURER AND MODEL NUMBER OF THE SYSTEM AND
 ELECTRICAL RATING (VOLTAGE AND CURRENT) OF THE
 CONTAINED BATTERY SYSTEM. SIGNS SHALL BE PROVIDED
 WITHIN BATTERY CABINETS TO INDICATE THE RELEVANT
 ELECTRICAL, CHEMICAL, AND FIRE HAZARD.
  
 52.3.6 VENTILATION. FOR FLOODED LEAD-ACID, FLOODED
 NICKEL-CADMIUM, AND VRLA BATTERIES, VENTILATION SHALL
 BE PROVIDED FOR ROOMS AND CABINETS IN ACCORDANCE WITH
 THE MECHANICAL CODE AND ONE OF THE FOLLOWING: (1) THE
 VENTILATION SYSTEM SHALL BE DESIGNED TO LIMIT THE
 MAXIMUM CONCENTRATION OF HYDROGEN TO 1.0 PERCENT OF THE
 TOTAL VOLUME OF THE ROOM DURING THE WORST-CASE EVENT OF
 SIMULTANEOUS ?BOOST? CHARGING OF ALL THE BATTERIES, IN
 ACCORDANCE WITH NATIONALLY RECOGNIZED STANDARDS. (2)
 CONTINUOUS VENTILATION SHALL BE PROVIDED AT A RATE OF
 NOT LESS THAN 1 FT3/MIN/FT2 (5.1 L/SEC/M2) OF FLOOR
 AREA OF THE ROOM OR CABINET.
  
 52.3.5 NEUTRALIZATION. AN APPROVED METHOD TO NEUTRALIZE
 SPILLED ELECTROLYTE SHALL BE PROVIDED.
  
 52.3.4 SPILL CONTROL. ROOMS, BUILDINGS, OR AREAS
 CONTAINING FREE-FLOWING LIQUID ELECTROLYTE IN
 INDIVIDUAL VESSELS HAVING A CAPACITY OF MORE THAN 55
 GAL (208 L) OR MULTIPLE VESSELS HAVING AN AGGREGATE
 CAPACITY EXCEEDING 1000 GAL (3785 L) SHALL BE PROVIDED
 WITH SPILL CONTROL TO PREVENT THE FLOW OF LIQUIDS TO
 ADJOINING AREAS.
  
 52.3.2 THERMAL RUNAWAY. VRLA, LITHIUM-ION, AND LITHIUM
 METAL POLYMER BATTERY SYSTEMS SHALL BE PROVIDED WITH A
 LISTED DEVICE OR OTHER APPROVED METHOD TO PRECLUDE,
 DETECT, AND CONTROL THERMAL RUNAWAY.
  
 SEPARATE PLANS AND PERMITS NEEDED FOR EMERGENCY
 GENERATOR AND DIESEL FUEL TANK.
  