Plan Review Notes
Plan Review Notes For Permit 13090544
Permit Number 13090544
Review Stop B
Sequence Number 1
Notes
Date Text
2013-09-24 13:21:44BUILDING PLAN REVIEW
 REVISION: 13090544
 PERMIT: 13080724
 ADD: 701 S ROSEMARY AVE # 151
 CONT: LAKEVIEW CONSTRUCTIONOF WISCONSIN
 TEL: (561635-6935
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 9/24/2013
 ACTION: DENIED
  
 1) SHEET A609 DETAIL # 5 INDICATES NEW WALL SIGN BUT NO
 WIND DESIGN CRITERIA IS GIVEN:
  
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 1.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2)
  
 2) DESIGNER DOES NOT PROVIDE HOW THE SIGN, LETTERS ARE
 GOING TO BE FASTENED TO THE BUILDING, TYPE OF ANCHOR,
 SIZE OF ANCHOR OR QUANTITY OF ANCHORS TO BE INSTALLED
 PER LETTER.
  
 3) THIS REVISION IS FOR SIGNS, SIGNS SHOULD COME IN
 UNDER A SEPERATE PERMIT NOT A REVISION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]