Plan Review Notes
Plan Review Notes For Permit 13090529
Permit Number 13090529
Review Stop B
Sequence Number 1
Notes
Date Text
2013-09-25 07:52:22BUILDING PLAN REVIEW
 PERMIT: 13090529
 ADD: 5600 N FLAGLER #406
 CONT: ALL CLAIMSINSURANCE REPAIRS
 TEL: (954)456-1650
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT 25/2013
 ACTION: DENIED
  
 1) SHEET A-1 DOES NOT INDICATE THE REPLACEMENT OF
 EXTERIOR DOORS, THE FLOOR PLAN DOES NOT INDICATE ANY
 WINDOWS IN THE EXTERIOR WALLS AT ALL, BUT PRODUCT
 APPROVALS WERE SUBMITTED FOR THE REPLACEMENT OF
 WINDOWS, NOT REVIED BY THE DESIGNER OF RECORD.
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) SHEET A 1 DOES NOT INDICATE WHAT PRESSURES THE
 WINDOWS AND EXTERIOR DOORS ARE TO BE DESIGNED FOR.
 THERE IS A SIGNED AND SEALED WIND DESIGN SHEET ATTACHED
 TO THE SLIDDING GLASS DOORS,
 THE WIND DESIGN IS WRONG;
 2A) WIND VELOCITY 150, PLEASE SEE 2010 FBC-B FIGURE
 1609A, RISK CATEGORY II BUILDING
 2B) EXPOSURE C PLEASE REVIEW 2010 FBC-B 1609.4.3
 EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND
 SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D,
 PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT
 LEAST 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL EXTEND
 INLAND FROM THE SHORELINE FOR A DISTANCE OF 600 FEET
 (183 M) OR 20 TIMES THE HEIGHT OF THE BUILDING,
 WHICHEVER IS GREATER FROM AN EXPOSURE D CONDITION AS
 DEFINED IN THE PREVIOUS SENTENCE.
 PLEASE REVISE WIND CALCULATIONS FOR BOTH THE WINDOWS
 AND DOORS WITH THE ABOVE LISTED ADJUSTMENTS.
  
 3) THE PERMIT APPLICATION AND PLANS INDICATE THIS UNIT
 IS LOCATED ON THE 4TH FLOOR, PLEASE CONFIRM IF THE
 GLAZING IS ABOVE OR BELOW 30 FEET ABOVE GRADE. IF 30
 THE OPENINGS ARE BELOW 30 FEET THEN LARGE MISSILE
 IMPACT RATED GLAZING IS REQUIRED, OR STORM SHUTTERS, IF
 ABOVE 30 FEET ABOVE GRADE THEN SMALL MISSILE IMPACT
 GLAZING IS REQUIRED AND SHUTTERS.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(E) SHUTTERS
  
 4) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4, 1714.5.1 &
 EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS,
 WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION TO FACILITATE
 PLAN REVIEW AND PERMIT ISSUANCE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676