Date |
Text |
2013-09-25 07:52:22 | BUILDING PLAN REVIEW |
| PERMIT: 13090529 |
| ADD: 5600 N FLAGLER #406 |
| CONT: ALL CLAIMSINSURANCE REPAIRS |
| TEL: (954)456-1650 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. SEPT 25/2013 |
| ACTION: DENIED |
| |
| 1) SHEET A-1 DOES NOT INDICATE THE REPLACEMENT OF |
| EXTERIOR DOORS, THE FLOOR PLAN DOES NOT INDICATE ANY |
| WINDOWS IN THE EXTERIOR WALLS AT ALL, BUT PRODUCT |
| APPROVALS WERE SUBMITTED FOR THE REPLACEMENT OF |
| WINDOWS, NOT REVIED BY THE DESIGNER OF RECORD. |
| 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 2) SHEET A 1 DOES NOT INDICATE WHAT PRESSURES THE |
| WINDOWS AND EXTERIOR DOORS ARE TO BE DESIGNED FOR. |
| THERE IS A SIGNED AND SEALED WIND DESIGN SHEET ATTACHED |
| TO THE SLIDDING GLASS DOORS, |
| THE WIND DESIGN IS WRONG; |
| 2A) WIND VELOCITY 150, PLEASE SEE 2010 FBC-B FIGURE |
| 1609A, RISK CATEGORY II BUILDING |
| 2B) EXPOSURE C PLEASE REVIEW 2010 FBC-B 1609.4.3 |
| EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND |
| SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D, |
| PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT |
| LEAST 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE |
| BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL EXTEND |
| INLAND FROM THE SHORELINE FOR A DISTANCE OF 600 FEET |
| (183 M) OR 20 TIMES THE HEIGHT OF THE BUILDING, |
| WHICHEVER IS GREATER FROM AN EXPOSURE D CONDITION AS |
| DEFINED IN THE PREVIOUS SENTENCE. |
| PLEASE REVISE WIND CALCULATIONS FOR BOTH THE WINDOWS |
| AND DOORS WITH THE ABOVE LISTED ADJUSTMENTS. |
| |
| 3) THE PERMIT APPLICATION AND PLANS INDICATE THIS UNIT |
| IS LOCATED ON THE 4TH FLOOR, PLEASE CONFIRM IF THE |
| GLAZING IS ABOVE OR BELOW 30 FEET ABOVE GRADE. IF 30 |
| THE OPENINGS ARE BELOW 30 FEET THEN LARGE MISSILE |
| IMPACT RATED GLAZING IS REQUIRED, OR STORM SHUTTERS, IF |
| ABOVE 30 FEET ABOVE GRADE THEN SMALL MISSILE IMPACT |
| GLAZING IS REQUIRED AND SHUTTERS. |
| |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(E) SHUTTERS |
| |
| 4) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| 1609.1.4. |
| |
| FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4, 1714.5.1 & |
| EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE |
| INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING |
| SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT |
| SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS, |
| WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION TO FACILITATE |
| PLAN REVIEW AND PERMIT ISSUANCE. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |