2013-09-20 17:49:372010 FBC
  
 DENIED BY PLUMBING
  
 1) THE INTELLIFLO VS 3050 POOL PUMP SPECIFIED ON SHEET
 2 OF THE PLANS HAS A MAXIMUM FLOW RATE OF 145 GPM WITH
 A 50' TDH. THE WATER VELOCITY IN THE 2-1/2 " SUCTION
 PIPING EXCEEDS THE 8 FEET PER SECOND ALLOWED BY FBCR
 4101.6.3. PLEASE CORRECT.
  