Plan Review Notes For Permit 13090506 |
Permit Number |
13090506 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2014-03-20 13:57:20 | REVISION SECOND PLUMBING REVIEW CHECKLIST. | | CODE: 2010 FBC. | | | | *** ORIGINAL COMMENT: | | 1- PROVIDE A CORRECT AND COMPLETE PLUMBING RISER | | DIAGRAM THAT MATCHES PROPOSED MASTER BATH AND RELOCATED | | HALF BATH BELOW STAIRS. SEC. 107.3.5.3(11) OF CITY | | AMENDMENTS TO FBC. | | | | *** PLUMBING RISER DIAGRAM SUBMITTED IS INCOMPLETE AND | | IS NOT CORRECT. TO AVOID MORE CONFUSION AND DELAYS, | | PLUMBING RISER DIAGRAM MAY BE DRAWN BY THE LICENSED | | CONTRACTOR RESPONSIBLE FOR THE WORK. | | | | | | |
|