2014-01-03 17:00:47REVISION PLUMBING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE A CORRECT AND COMPLETE PLUMBING RISER
 DIAGRAM THAT MATCHES PROPOSED MASTER BATH AND RELOCATED
 HALF BATH BELOW STAIRS. SEC. 107.3.5.3(11) OF CITY
 AMENDMENTS TO FBC.
  
 2- PROVIDE DIMENSIONS FOR MASTER BATH FIXTURES TO SHOW
 COMPLIANCE WITH SEC. P2705 OF 2010 FBC-RESIDENTIAL.
  
 3- PROVIDE DIMENSIONS FOR MASTER BATHROOM SHOWER TO
 SHOW COMPLIANCE WITH SEC. P2708 OF 2010
 FBC-RESIDENTIAL.
  
 4- RELOCATION OF HALF BATHROOM FIXTURES REQUIRES THE
 FIXTURES TO COMPLY WITH SEC. P2705 OF 2010
 FBC-RESIDENTIAL. PROVIDE DIMENSIONS TO VERIFY
 COMPLIANCE WITH THE REQUIRED CLEARANCES.
  