Plan Review Notes For Permit 13090506 |
Permit Number |
13090506 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-10-31 16:58:44 | 10/31/2014 | | PROJECT: | | PERMIT#: 14080234 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | ELECTRICAL PLAN REVIEW | | ACTION: APPROVED WITH EXCEPTION. | | | | 1) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL | | 314 AND 315. INTERCONNECTED SMOKE DETECTORS ARE NOTED | | ON THE PLAN. HOWEVER WHEN THERE IS GAS OR A FIREPLACE | | THERE NEEDS TO BE CO DETECTORS WITH 10' OF SLEEPING | | AREAS. PLEASE COMPLY WITH FBC-R 314-315 | | | | 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER | | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11. | | | | 3) RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT | | MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL | | SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE | | OUTLET. NEC 210.52(A)(1) | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|