Plan Review Notes For Permit 13090506 |
Permit Number |
13090506 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-01-03 16:32:16 | REVISION MECHANICAL REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- PROVIDE COMPLETE A/C PLANS SHOWING ALL THE EQUIPMENT | | AND DUCTWORK. SEC. 103.2.2 OF 2010 FBC-ENERGY | | CONSERVATION. | | | | 2- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS AS | | REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | ***NOTE: EQUIPMENT LISTED ON THE EQUIPMENT SIZING | | CALCULATIONS TO MATCH EQUIPMENT SHOWN ON THE A/C PLAN. | | | | 3- PLANS SUBMITTED SHOW AN A/C UNIT INSIDE AN INTERIOR | | CLOSET ON THE SECOND FLOOR AND AN AHU ON THE ROOF ABOVE | | THE KITCHEN. CLARIFY AS REQUIRED. WHY THE AHU IS | | OUTSIDE?. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. | | | | 4- PROVIDE COMPLETE INSTALLATION DETAILS FOR THE | | ANCHORAGE OF UNIT LOCATED ON THE ROOF AS REQUIRED BY | | SEC. M1307.2.1 OF 2010 FBC-RESIDENTIAL. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|