2013-10-23 16:13:09IN ADDITION TO OTHER DISCREPANCIES NOTE NOTED, A FEW
 CHANGES AND CORRECTIONS WILL HAVE TO TAKE PLACE ON THE
 JOB FOR SUCCESSFUL INSPECTIONS:
 1. THE PLANS CURRENTLY CALL FOR AFCI ONLY IN THE
 BEDROOMS, NEC 2008 STATES DIFFERENTLY.
 2. TAMPER-RESISTANT RECEPTACLES SHALL BE REQUIRED
 THROUGH OUT THE HOME.
 3. ALL EXTERIOR RECEPTACLE SHALL BE RATED "WR"
 4. DUE TO THE GAS FIRE PLACE, CARBON MONOXIDE DETECTORS
 SHALL BE REQUIRED WITHIN 10' OF THE SLEEPING AREAS.