Plan Review Notes
Plan Review Notes For Permit 13090506
Permit Number 13090506
Review Stop B
Sequence Number 1
Notes
Date Text
2013-09-26 09:32:10RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1-ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE CORRECT BUILDER'S NAME. SEC. 103.2.1.1.2
 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) PROVIDE MANUFACTURER'S DOCUMENTATION SHOWING THE
 WINDOWS U-FACTOR AND SHGC FACTOR AS SPECIFIED ON ITEM
 #7(A). SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 C) CALCULATIONS NEED TO BE CERTIFIED AND DATED AT THE
 BOTTOM OF THE FORM BY THE PERSON WHO PREPARED THEM.
 SEC. 405.4.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 D) ITEM #9(A) SPECIFIES R-13 IN EXTERIOR WALLS. TYPICAL
 WALL DETAIL ON FLOOR PLANS SUBMITTED SPECIFY R-11.
 REVISE AS REQUIRED TO MATCH. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 E) REVISE THE OVERHANG DEPTH AND SEPARATION SPECIFIED
 FOR THE WINDOWS ON PAGE 4 OF 6 TO MATCH HOUSE.
  
 ***NOTE: THIS IS A 2 STORY HOUSE WITH FLAT ROOF AND NO
 OVERHANGS.
  
 2- PLANS SUBMITTED NEED TO BE SIGNED AND DATED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
  
 ****REMAINDER: THE FOLLOWING INFORMATION NEED TO BE
 PROVIDED.
  
 1- PROVIDE PRODUCT APPROVAL FOR EXTERIOR DOORS (AS
 REQUESTED ON PROVISO. (SEE APPROVED PLANS).
  
 2- PROVIDE COMPLETE INFORMATION FOR A/C UNDER A
 SEPARATE PERMIT. (NO INFORMATION SUBMITTED YET).
  
  
 ********* PLEASE PROVIDE A RESPONSE LETTER ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS********
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712