2013-09-26 09:32:10 | RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1-ENERGY CALCULATIONS SUBMITTED: |
| A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING THE CORRECT BUILDER'S NAME. SEC. 103.2.1.1.2 |
| OF 2010 FBC-ENERGY CONSERVATION. |
| |
| B) PROVIDE MANUFACTURER'S DOCUMENTATION SHOWING THE |
| WINDOWS U-FACTOR AND SHGC FACTOR AS SPECIFIED ON ITEM |
| #7(A). SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| C) CALCULATIONS NEED TO BE CERTIFIED AND DATED AT THE |
| BOTTOM OF THE FORM BY THE PERSON WHO PREPARED THEM. |
| SEC. 405.4.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| D) ITEM #9(A) SPECIFIES R-13 IN EXTERIOR WALLS. TYPICAL |
| WALL DETAIL ON FLOOR PLANS SUBMITTED SPECIFY R-11. |
| REVISE AS REQUIRED TO MATCH. SEC. 103.2.2 OF 2010 |
| FBC-ENERGY CONSERVATION. |
| |
| E) REVISE THE OVERHANG DEPTH AND SEPARATION SPECIFIED |
| FOR THE WINDOWS ON PAGE 4 OF 6 TO MATCH HOUSE. |
| |
| ***NOTE: THIS IS A 2 STORY HOUSE WITH FLAT ROOF AND NO |
| OVERHANGS. |
| |
| 2- PLANS SUBMITTED NEED TO BE SIGNED AND DATED BY THE |
| PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 CITY |
| AMENDMENTS TO FBC. |
| |
| |
| ****REMAINDER: THE FOLLOWING INFORMATION NEED TO BE |
| PROVIDED. |
| |
| 1- PROVIDE PRODUCT APPROVAL FOR EXTERIOR DOORS (AS |
| REQUESTED ON PROVISO. (SEE APPROVED PLANS). |
| |
| 2- PROVIDE COMPLETE INFORMATION FOR A/C UNDER A |
| SEPARATE PERMIT. (NO INFORMATION SUBMITTED YET). |
| |
| |
| ********* PLEASE PROVIDE A RESPONSE LETTER ADDRESSING |
| EACH COMMENT TO EXPEDITE THE REVIEW PROCESS******** |
| |
| |