Plan Review Notes
Plan Review Notes For Permit 13090380
Permit Number 13090380
Review Stop M
Sequence Number 1
Notes
Date Text
2013-09-16 09:12:45RESIDENTIAL R(3) A/C REVISION MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL.
  
 1- CONTRACTOR NEED TO APPLY FOR MECHANICAL PERMIT AS
 REQUESTED ON PROVISO DATED 5/28/13. SEC. 105.1 CITY
 AMENDMENTS TO FBC.
  
 2- SIZE OF RETURN AIR FOR A)MASTER BEDROOM, B) BEDROOM
 #2 AND C)BEDROOM #3 DON'T COMPLY WITH SEC. M1602.4
 EXCEPTION #1 AND #3. REVISE AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712